Plan Review Notes
Plan Review Notes For Permit 14040657
Permit Number 14040657
Review Stop P
Sequence Number 1
Notes
Date Text
2014-05-03 13:27:53PERMIT: 14040657
 ADD: 5335 N MILITARY TRL. # 40 & 65
 CONT: MIKE MOORE
 TEL: (561) 301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 03/ 2014
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET A-1;
  
 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A
 MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE
 BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010
 FBC-B 508.2 & 508.2.1.
  
 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS
 BEING FIGURED AT 35 SQ FT INTHE CLASSROOMS, NOTE THIS
 IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL
 OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE
 FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES
 AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER
 ALL OCCUPANTLOAD AND POSSIBLE PLUMBING FIXTURE COUNT.
 PLEASE PROVIDE A FIXTURE COUNT PER 2010 FBC-PLUMBING
 TABLE 403.1.
  
 1C) THE EXISTING RESTROOMS LOCATED BY THE LAUNDRY ROOM
 ARE NOT ACCESSIBLE PLEASE SHOW COMPLIANCE WITH 2010
 FBC-P 213 TOILET FACILITIES AND BATHING FACILITIES
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603. EXC. 4. WHERE
 MULTIPLE SINGLE USER TOILET ROOMS ARE CLUSTERED AT A
 SINGLE LOCATION, NO MORE THAN 50 PERCENT OF THE SINGLE
 USER TOILET ROOMS FOR EACH USE AT EACH CLUSTER SHALL BE
 REQUIRED TO COMPLY WITH 603.
  
 1D) SHEET A-2 PROVIDES HANDICAPPED DETAILS FOR ADULTS
 BUT DOES NOT ADDRESS THE FOLLOWING ACCESSIBILITY
 REQUIEMENTS:
 2010 FBC- ACCESSIBILITY CODE;
 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9. SEE AGES 3 & 4, AGES 5-8 &
 9-12.
 604.9.1 LOCATION.
 THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM
 AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR
 RIGHT-HAND APPROACH TO THE WATER CLOSET.
  
 604.9.2 CLEARANCE.
 CLEARANCE AROUND A WATER CLOSET SHALL COMPLY WITH
 604.3.
  
 604.9.3 HEIGHT.
 THE HEIGHT OF WATER CLOSETS SHALL BE 11 INCHES (280 MM)
 MINIMUM AND 17 INCHES (430 MM) MAXIMUM MEASURED TO THE
 TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION.
  
 604.9.4 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 604.5.
  
 604.9.5 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.2
 AND 309.4 AND SHALL BE INSTALLED 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR. FLUSH CONTROLS SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN
 AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH
 604.8.2.
  
 604.9.6 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 14 INCHES (355 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM ABOVE THE FINISH FLOOR. THERE
 SHALL BE A CLEARANCE OF 11/2 INCHES (38 MM) MINIMUM
 BELOW THE GRAB BAR. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 2) SHEET A2 VENT SIZES ARE NOT PROVIDED ON THE DETAIL
 INACCORDANCE WITH 2010 FBC-P 907.1 & 908.1.
  
 3) THE PLANS DO NOT SHOW POTABLE WATER: 602.2 POTABLE
 WATER REQUIRED.
 ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING
 FIXTURES THAT PROVIDE WATER FOR DRINKING, BATHING OR
 CULINARY PURPOSES, OR FOR THE PROCESSING OF FOOD,
 MEDICAL OR PHARMACEUTICAL PRODUCTS. UNLESS OTHERWISE
 PROVIDED IN THIS CODE, POTABLE WATER SHALL BE SUPPLIED
 TO ALL PLUMBING FIXTURE
  
 4) HOT WATER REQUIRED. 607.1 WHERE REQUIRED.
 IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO
 ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE.
  
 EXCEPTION: IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR
 TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND
 WASHING PURPOSES. THE DELIVERY OF COLD WATER ONLY SHALL
 BE PERMITTED TO BE DELIVERED FROM ALL HAND WASHING
 FACILITIES EXCEPT WHERE HOT WATER IS REQUIRED BY LAW.
  
 607.1.1 HAND WASHING LAVATORIES.
 IN PUBLIC FOOD SERVICE ESTABLISHMENTS, FOOD
 ESTABLISHMENTS OR WHERE OTHERWISE REQUIRED BY LAW,
 LAVATORIES INTENDED FOR THE PURPOSE OF EMPLOYEE HAND
 WASHING SHALL BE EQUIPPED WITH HOT OR TEMPERED WATER.
  
 5) THE FOOD PREP AREA DOES NOT INDICATE COMPLIANCE WITH
 2010 FBC-PLUMBING 1003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved