Date |
Text |
2014-05-03 13:27:53 | PERMIT: 14040657 |
| ADD: 5335 N MILITARY TRL. # 40 & 65 |
| CONT: MIKE MOORE |
| TEL: (561) 301-9468 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. MAY 03/ 2014 |
| ACTION: DENIED |
| |
| 1) LIFE SAFETY SHEET A-1; |
| |
| 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A |
| MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE |
| BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010 |
| FBC-B 508.2 & 508.2.1. |
| |
| 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS |
| BEING FIGURED AT 35 SQ FT INTHE CLASSROOMS, NOTE THIS |
| IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL |
| OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE |
| FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES |
| AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER |
| ALL OCCUPANTLOAD AND POSSIBLE PLUMBING FIXTURE COUNT. |
| PLEASE PROVIDE A FIXTURE COUNT PER 2010 FBC-PLUMBING |
| TABLE 403.1. |
| |
| 1C) THE EXISTING RESTROOMS LOCATED BY THE LAUNDRY ROOM |
| ARE NOT ACCESSIBLE PLEASE SHOW COMPLIANCE WITH 2010 |
| FBC-P 213 TOILET FACILITIES AND BATHING FACILITIES |
| 213.2 TOILET ROOMS AND BATHING ROOMS. |
| WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH |
| BATHING ROOM SHALL COMPLY WITH 603. EXC. 4. WHERE |
| MULTIPLE SINGLE USER TOILET ROOMS ARE CLUSTERED AT A |
| SINGLE LOCATION, NO MORE THAN 50 PERCENT OF THE SINGLE |
| USER TOILET ROOMS FOR EACH USE AT EACH CLUSTER SHALL BE |
| REQUIRED TO COMPLY WITH 603. |
| |
| 1D) SHEET A-2 PROVIDES HANDICAPPED DETAILS FOR ADULTS |
| BUT DOES NOT ADDRESS THE FOLLOWING ACCESSIBILITY |
| REQUIEMENTS: |
| 2010 FBC- ACCESSIBILITY CODE; |
| 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| CHILDREN?S USE. |
| WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S |
| USE SHALL COMPLY WITH 604.9. SEE AGES 3 & 4, AGES 5-8 & |
| 9-12. |
| 604.9.1 LOCATION. |
| THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM |
| AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR |
| RIGHT-HAND APPROACH TO THE WATER CLOSET. |
| |
| 604.9.2 CLEARANCE. |
| CLEARANCE AROUND A WATER CLOSET SHALL COMPLY WITH |
| 604.3. |
| |
| 604.9.3 HEIGHT. |
| THE HEIGHT OF WATER CLOSETS SHALL BE 11 INCHES (280 MM) |
| MINIMUM AND 17 INCHES (430 MM) MAXIMUM MEASURED TO THE |
| TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO |
| A LIFTED POSITION. |
| |
| 604.9.4 GRAB BARS. |
| GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 604.5. |
| |
| 604.9.5 FLUSH CONTROLS. |
| FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.2 |
| AND 309.4 AND SHALL BE INSTALLED 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR. FLUSH CONTROLS SHALL BE |
| LOCATED ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN |
| AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH |
| 604.8.2. |
| |
| 604.9.6 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 14 INCHES (355 MM) MINIMUM AND 19 |
| INCHES (485 MM) MAXIMUM ABOVE THE FINISH FLOOR. THERE |
| SHALL BE A CLEARANCE OF 11/2 INCHES (38 MM) MINIMUM |
| BELOW THE GRAB BAR. DISPENSERS SHALL NOT BE OF A TYPE |
| THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW |
| CONTINUOUS PAPER FLOW. |
| |
| 2) SHEET A2 VENT SIZES ARE NOT PROVIDED ON THE DETAIL |
| INACCORDANCE WITH 2010 FBC-P 907.1 & 908.1. |
| |
| 3) THE PLANS DO NOT SHOW POTABLE WATER: 602.2 POTABLE |
| WATER REQUIRED. |
| ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING |
| FIXTURES THAT PROVIDE WATER FOR DRINKING, BATHING OR |
| CULINARY PURPOSES, OR FOR THE PROCESSING OF FOOD, |
| MEDICAL OR PHARMACEUTICAL PRODUCTS. UNLESS OTHERWISE |
| PROVIDED IN THIS CODE, POTABLE WATER SHALL BE SUPPLIED |
| TO ALL PLUMBING FIXTURE |
| |
| 4) HOT WATER REQUIRED. 607.1 WHERE REQUIRED. |
| IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO |
| ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR |
| BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY |
| OR BUILDING MAINTENANCE. |
| |
| EXCEPTION: IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR |
| TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND |
| WASHING PURPOSES. THE DELIVERY OF COLD WATER ONLY SHALL |
| BE PERMITTED TO BE DELIVERED FROM ALL HAND WASHING |
| FACILITIES EXCEPT WHERE HOT WATER IS REQUIRED BY LAW. |
| |
| 607.1.1 HAND WASHING LAVATORIES. |
| IN PUBLIC FOOD SERVICE ESTABLISHMENTS, FOOD |
| ESTABLISHMENTS OR WHERE OTHERWISE REQUIRED BY LAW, |
| LAVATORIES INTENDED FOR THE PURPOSE OF EMPLOYEE HAND |
| WASHING SHALL BE EQUIPPED WITH HOT OR TEMPERED WATER. |
| |
| 5) THE FOOD PREP AREA DOES NOT INDICATE COMPLIANCE WITH |
| 2010 FBC-PLUMBING 1003.3.1 GREASE INTERCEPTORS AND |
| AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. |
| A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL |
| KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY |
| CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL |
| INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR |
| SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS |
| INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT |
| ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |