Plan Review Notes
Plan Review Notes For Permit 14040657
Permit Number 14040657
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-22 14:46:16THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMNETS.
  
 ON SHEETS LS-1 AND E-2, PLEASE ADD AN "EM" LIGHT IN
 REAR HALLWAY WHERE INDICATED AND MOVE THE "EM" LIGHT
 FROM LEFT SIDE OF HALLWAY TO THE RIGHT SIDE.
  
 ON SHEET E-1 AT THE FRONT LOBBY AND RECEPTION AREA IT
 INDICATES "BUZZER RELEASE". THE EXIT DOORS IN THAT AREA
 CAN'T BE LOCKED AGAINST EGRESS. PLEASE REFER TO THE
 DELAYED EGRESS CODE IN CHAPTER 7 OF THE FLORIDA FIRE
 PREVENTION CODE FOR GUIDENCE.