Plan Review Notes
Plan Review Notes For Permit 14040657
Permit Number 14040657
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-12 13:15:40ELECTRICAL PROVISO:
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE
 701.11(G) OF THE 2008 EDITION OF THE NEC.
  
 3) CONDUCTORS SHALL BE PERMITTED TO BE TAPPED WITHOUT
 OVERCURRENT PROTECTION AT THE TAP TO A FEEDER AS
 SPECIFIED IN 240.21(B)(1) THROUGH B(5) SEE ARTICLE
 240.21(B) OF THE 2008 EDITION OF THE NEC. THE RISER
 DIAGRAM AS SHOWN ON PLANS DOES NOT APPEAR TO BE IN
 COMPLIANCE. VERIFY EXISTING CONDITION IN THE FIELD.
  
 4) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW
 VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE
 ALARM, DATA/COM, AND ACCESS CONTROL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  