Plan Review Notes
Plan Review Notes For Permit 14040657
Permit Number 14040657
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-05 08:52:17BUILDING PLAN REVIW
 PERMIT: 14040657
 ADD: 5335 N MILITARY TRL. # 40 & 65
 CONT: MIKE MOORE
 TEL: (561) 301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 03/ 2014
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET A-1;
  
 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A
 MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE
 BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010
 FBC-B 508.2 & 508.2.1.
  
 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS
 BEING FIGURED AT 35 SQ FT IN THE CLASSROOMS, NOTE THIS
 IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL
 OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE
 FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES
 AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER
 ALL OCCUPANT LOAD AND POSSIBLE PLUMBING FIXTURE COUNT.
  
 1C) WITH THE INCREASED OCCUPANT LOAD IN CLASSROOM # 6
 AND THE MULTI-PURPOSE ROOM EACH HAVING A OCCUPANT LOAD
 GREATER THAN 49 WILL REQUIRE 2 EXIT DOORS SEE 2010
 FBC-B TABLE 1015.1.
  
 1D) THE 2 ROOMS REQUIRING THE 2 EGRESS EXIT DOORS WILL
 ALSO NEED TO COMPLY WITH THE 2 DOORS BEING 1/3RD THE
 DIAGONAL DISTANCE APART IN EACH ROOM SEE 2010 FBC-B
 1015.2.1 EXC. 2.
  
 1E) PLEASE PROVIDE A EXPLANATION AS TO THE TERM
 CLASSROOM AND WHAT WILL BE TAUGHT IN EACH AREA, SEE HOW
 THIS TERM AFFECTS THE OCCUPANCY AND WALL RATINGS.
 2010 FBC-B 313.1 SCOPE.
 GROUP D OCCUPANCY IS THE USE OF A BUILDING OR
 STRUCTURE, OR ANY PORTION THEREOF, IN WHICH THREE OR
 MORE CLIENTS RECEIVE CARE, MAINTENANCE AND SUPERVISION,
 BY OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S),
 FOR LESS THAN 24 HOURS PER DAY. OCCUPANCIES THAT
 INCLUDE PART-DAY PRESCHOOLS, KINDERGARTENS AND OTHER
 SCHOOLS WHOSE PURPOSE IS PRIMARILY EDUCATIONAL EVEN
 THOUGH THE CHILDREN ARE OF PRESCHOOL AGE SHALL COMPLY
 WITH THE PROVISIONS FOR GROUP E OCCUPANCIES.
  
 1F) CORRIDOR WIDTHS WILL NEED TO BE INCREASED TO COMPLY
 WITH 2010 FBC-B 1018.2 CORRIDOR WIDTH.
 THE MINIMUM CORRIDOR WIDTH SHALL BE AS DETERMINED IN
 SECTION 1005.1, BUT NOT LESS THAN 44 INCHES (1118 MM).
 EXC. 4. SEVENTY-TWO INCHES (1829 MM)?IN GROUP E WITH A
 CORRIDOR HAVING A REQUIRED CAPACITY OF 100 OR MORE.
  
 1G) CORRIDOR WALL SECTIONS DETAILS 7/A3 & DETAIL #8/A3
 BOTH INDICATE THE USE OF SMOKE PARTITIONS, PLEASE SEE
 THE INFORMAL BOAF INTERPRETATION ON SMOKE PARTITIONS
 AND DRYWALL ON ONE SIDE ONLY.
 DATE: MON OCT 26 2009
 REPORT: 6341
 CODE: BUILDING CODE YEAR: 2007
 SECTION: 710
 QUESTION:
 IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING
 SECTION 710.4 TO ALLOW A SMOKE PARTITION TO BE
 CONSTRUCTED WITH ONE LAYER OF
 GYPSUM WALLBOARD ON ONE SIDE (THE SMOKE SIDE) OF THE
 PARTITION OR MUST WALLBOARD BE INSTALLED ON BOTH SIDES,
 EXTENDING FROM
 FOUNDATION OR FLOOR TO THE UNDERSIDE OF THE FLOOR OR
 ROOF SHEATHING, DECK OR SLAB ABOVE?
 COMMENT:
 NONE.
 ANSWER:
 YES. ONE LAYER OF GYPSUM ON ONE SIDE IS ACCEPTABLE BUT
 THE OTHER SIDE CANNOT REMAIN OPEN. IT MUST BE ENCLOSED
 WITH MATERIAL
 "PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION". THE
 WALL MUST BE ENCLOSED FROM BOTH SIDES TO PREVENT SMOKE
 MIGRATION FROM
 EITHER SIDE. THE SPACE AROUND PENETRATING ITEMS AND IN
 JOINTS SHALL BE FILLED WITH AN APPROVED MATERIAL TO
 LIMIT THE FREE PASSAGE
 OF SMOKE. THE WALL MAY HAVE ELECTRICAL BOXES OR OTHER
 PENETRATIONS THAT CAN ALLOW SMOKE TO MIGRATE FROM THE
 "OPEN" SIDE.
 COMMENTARY:
 SEE ALSO SECTIONS 710.2 AND 710.6.
  
 2A) SHEET A-3 DETAIL # 9 WALL AND CEILING OF THE
 LAUNDRY ROOM. THE PLANS INDICATE THE USE OF THE GYPSUM
 ASSOC. GA-610-02, GA FILES RC2601 & FC 5406, PLEASE
 PROVIDE THE DOCUMENTS SO THE INSPECTOR WILL BE ABLE TO
 DO THEIR INSPECTIONS. 107.2.1.3 ADDITIONAL INFORMAION
 REQUIRED. 707.5 CONTINUITY.
  
 2B) THIS SAME DETAIL ALSO INDICATES THE USE OF AN
 ALTERNANTE HORIZONTAL ASSEMBLY AER-09038 FIG. # 7. SEE
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 2C) 707.9 DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS
 IN A FIRE BARRIER BY DUCTS AND AIR TRANSFER OPENINGS
 SHALL COMPLY WITH SECTION 716.
  
 3) SHEET A-2 DETAIL # 10 INDICATES NEW OPENING IN A
 EXTERIOR CMU WALL. SHEET A-1 DOES NOT SHOW THIS DETAIL
 ANYWHERE. CLASSROOM # 4 DOOR # 1 DOES SHOW POSITIVE &
 NEGATIVE PRESSURES, ASSUMING THIS IS THE NEW DOOR.
  
 3A) SHEET A-2 DETAIL # 10 SHOWS A NEW LINTAL BUT DOES
 NOT INDICATE HOW THE VERTICAL REBARS THAT ARE BEING CUT
 WILL MAINTAIN THE PART OF THE MAIN WIND FORCE
 RESISTNING SYSTEM (MWERS)? 1609.6.
  
 3B) SHEET A1 CLASSROOM # 4 DOOR # 1 INDICATE PRESSURES
 PLEASE PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B
 1609.6.
  
  
 3C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3D) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715