2014-05-05 08:52:17 | BUILDING PLAN REVIW |
| PERMIT: 14040657 |
| ADD: 5335 N MILITARY TRL. # 40 & 65 |
| CONT: MIKE MOORE |
| TEL: (561) 301-9468 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. MAY 03/ 2014 |
| ACTION: DENIED |
| |
| 1) LIFE SAFETY SHEET A-1; |
| |
| 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A |
| MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE |
| BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010 |
| FBC-B 508.2 & 508.2.1. |
| |
| 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS |
| BEING FIGURED AT 35 SQ FT IN THE CLASSROOMS, NOTE THIS |
| IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL |
| OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE |
| FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES |
| AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER |
| ALL OCCUPANT LOAD AND POSSIBLE PLUMBING FIXTURE COUNT. |
| |
| 1C) WITH THE INCREASED OCCUPANT LOAD IN CLASSROOM # 6 |
| AND THE MULTI-PURPOSE ROOM EACH HAVING A OCCUPANT LOAD |
| GREATER THAN 49 WILL REQUIRE 2 EXIT DOORS SEE 2010 |
| FBC-B TABLE 1015.1. |
| |
| 1D) THE 2 ROOMS REQUIRING THE 2 EGRESS EXIT DOORS WILL |
| ALSO NEED TO COMPLY WITH THE 2 DOORS BEING 1/3RD THE |
| DIAGONAL DISTANCE APART IN EACH ROOM SEE 2010 FBC-B |
| 1015.2.1 EXC. 2. |
| |
| 1E) PLEASE PROVIDE A EXPLANATION AS TO THE TERM |
| CLASSROOM AND WHAT WILL BE TAUGHT IN EACH AREA, SEE HOW |
| THIS TERM AFFECTS THE OCCUPANCY AND WALL RATINGS. |
| 2010 FBC-B 313.1 SCOPE. |
| GROUP D OCCUPANCY IS THE USE OF A BUILDING OR |
| STRUCTURE, OR ANY PORTION THEREOF, IN WHICH THREE OR |
| MORE CLIENTS RECEIVE CARE, MAINTENANCE AND SUPERVISION, |
| BY OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S), |
| FOR LESS THAN 24 HOURS PER DAY. OCCUPANCIES THAT |
| INCLUDE PART-DAY PRESCHOOLS, KINDERGARTENS AND OTHER |
| SCHOOLS WHOSE PURPOSE IS PRIMARILY EDUCATIONAL EVEN |
| THOUGH THE CHILDREN ARE OF PRESCHOOL AGE SHALL COMPLY |
| WITH THE PROVISIONS FOR GROUP E OCCUPANCIES. |
| |
| 1F) CORRIDOR WIDTHS WILL NEED TO BE INCREASED TO COMPLY |
| WITH 2010 FBC-B 1018.2 CORRIDOR WIDTH. |
| THE MINIMUM CORRIDOR WIDTH SHALL BE AS DETERMINED IN |
| SECTION 1005.1, BUT NOT LESS THAN 44 INCHES (1118 MM). |
| EXC. 4. SEVENTY-TWO INCHES (1829 MM)?IN GROUP E WITH A |
| CORRIDOR HAVING A REQUIRED CAPACITY OF 100 OR MORE. |
| |
| 1G) CORRIDOR WALL SECTIONS DETAILS 7/A3 & DETAIL #8/A3 |
| BOTH INDICATE THE USE OF SMOKE PARTITIONS, PLEASE SEE |
| THE INFORMAL BOAF INTERPRETATION ON SMOKE PARTITIONS |
| AND DRYWALL ON ONE SIDE ONLY. |
| DATE: MON OCT 26 2009 |
| REPORT: 6341 |
| CODE: BUILDING CODE YEAR: 2007 |
| SECTION: 710 |
| QUESTION: |
| IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING |
| SECTION 710.4 TO ALLOW A SMOKE PARTITION TO BE |
| CONSTRUCTED WITH ONE LAYER OF |
| GYPSUM WALLBOARD ON ONE SIDE (THE SMOKE SIDE) OF THE |
| PARTITION OR MUST WALLBOARD BE INSTALLED ON BOTH SIDES, |
| EXTENDING FROM |
| FOUNDATION OR FLOOR TO THE UNDERSIDE OF THE FLOOR OR |
| ROOF SHEATHING, DECK OR SLAB ABOVE? |
| COMMENT: |
| NONE. |
| ANSWER: |
| YES. ONE LAYER OF GYPSUM ON ONE SIDE IS ACCEPTABLE BUT |
| THE OTHER SIDE CANNOT REMAIN OPEN. IT MUST BE ENCLOSED |
| WITH MATERIAL |
| "PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION". THE |
| WALL MUST BE ENCLOSED FROM BOTH SIDES TO PREVENT SMOKE |
| MIGRATION FROM |
| EITHER SIDE. THE SPACE AROUND PENETRATING ITEMS AND IN |
| JOINTS SHALL BE FILLED WITH AN APPROVED MATERIAL TO |
| LIMIT THE FREE PASSAGE |
| OF SMOKE. THE WALL MAY HAVE ELECTRICAL BOXES OR OTHER |
| PENETRATIONS THAT CAN ALLOW SMOKE TO MIGRATE FROM THE |
| "OPEN" SIDE. |
| COMMENTARY: |
| SEE ALSO SECTIONS 710.2 AND 710.6. |
| |
| 2A) SHEET A-3 DETAIL # 9 WALL AND CEILING OF THE |
| LAUNDRY ROOM. THE PLANS INDICATE THE USE OF THE GYPSUM |
| ASSOC. GA-610-02, GA FILES RC2601 & FC 5406, PLEASE |
| PROVIDE THE DOCUMENTS SO THE INSPECTOR WILL BE ABLE TO |
| DO THEIR INSPECTIONS. 107.2.1.3 ADDITIONAL INFORMAION |
| REQUIRED. 707.5 CONTINUITY. |
| |
| 2B) THIS SAME DETAIL ALSO INDICATES THE USE OF AN |
| ALTERNANTE HORIZONTAL ASSEMBLY AER-09038 FIG. # 7. SEE |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| |
| 2C) 707.9 DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS |
| IN A FIRE BARRIER BY DUCTS AND AIR TRANSFER OPENINGS |
| SHALL COMPLY WITH SECTION 716. |
| |
| 3) SHEET A-2 DETAIL # 10 INDICATES NEW OPENING IN A |
| EXTERIOR CMU WALL. SHEET A-1 DOES NOT SHOW THIS DETAIL |
| ANYWHERE. CLASSROOM # 4 DOOR # 1 DOES SHOW POSITIVE & |
| NEGATIVE PRESSURES, ASSUMING THIS IS THE NEW DOOR. |
| |
| 3A) SHEET A-2 DETAIL # 10 SHOWS A NEW LINTAL BUT DOES |
| NOT INDICATE HOW THE VERTICAL REBARS THAT ARE BEING CUT |
| WILL MAINTAIN THE PART OF THE MAIN WIND FORCE |
| RESISTNING SYSTEM (MWERS)? 1609.6. |
| |
| 3B) SHEET A1 CLASSROOM # 4 DOOR # 1 INDICATE PRESSURES |
| PLEASE PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B |
| 1609.6. |
| |
| |
| 3C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 3D) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |