Plan Review Notes For Permit 14040651 |
Permit Number |
14040651 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-05-03 06:51:23 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) THE BATHROOM IS NOT PROPERLY VENTED. FBCR P3108.2.1 | | NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | CONNECTION. | | | | 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE PLUMBING DESIGN IS REQUIRED ON THE | | PLUMBING PLANS. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|