Plan Review Notes For Permit 14040651 |
Permit Number |
14040651 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-21 14:14:22 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) SHOW COMPLIANCE WITH FBC R314 FOR SMOKE ALARMS. | | | | 2) SHOW COMPLIANCE WITH NEC 210.11 (C) (3) WHICH | | REQUIRES AT LEAST ONE 20 AMP BRANCH CIRCUIT TO SUPPLY | | BATHROOM RECEPTACLE OUTLETS. | | | | 3) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER RESISTANT | | RECETACLES. | | | | 4) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR AFCI | | PROTECTION. | | | | 5) THE PRINTED NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | PLANS. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|