Plan Review Notes For Permit 14040650 |
Permit Number |
14040650 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-22 11:45:41 | NEC | | TABLE 310.15(B)(6) CONDUCTOR TYPES AND SIZES FOR | | 120/240-VOLT, 3-WIRE, SINGLE-PHASE DWELLING SERVICES | | AND FEEDERS. | | THE PLAN SUBMITTED INDICATES A 1/0? IN 2" C. PLEASE | | INDICATE THE APPROPRIATE SIZE OF WIRE TO FEED A 200AMP | | MAIN INCLUDING THE MATERIAL (ALUMINUM OR COPPER) AND | | THE INSULLATION TYPE. | | | | 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS | | SHALL BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B), | | AND (C). | | PLEASE PROVIDE ADDITIONAL LIGHTING OUTLETS PER 210.70 | | OR INDICATE ON THE PLANS THAT THE PROJECT IS ALREADY IN | | COMPLIANCE. | | | | FBC 107.2.1 "CONSTRUCTION DOCUMENTS SHOULD BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF WORK PROPOSED. " | | THE PLAN'S RISER SUBMITTED INDICATES A DISC.? JUST TO | | THE LEFT OF THE METER. PLEASE INDICATE WHAT THIS IS, | | HOW IT IS FED, AND WHAT IT FEEDS. | | | | |
|