2014-04-29 16:43:36 | BUILDING PLAN REVIEW |
| PERMIT: 14040504 |
| ADD: 207 CLEMATIS ST. |
| CONT: GEORGE FRAKER |
| TEL: (561)502-4699 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUESDAY APRIL 29/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET # 1 THE FRONT ELEVATION SHOWS THE USE OF A |
| 22'-0" LONG HORIZONTAL MULLION. THE PRODUCT APPROVAL |
| SUBMITTED NOA 11-0922.01 |
| LONGEST SPAN OF 13.33 FT OR 160 INCHES. PLEASE PROVIDE |
| A STRUCTURAL ELEMENT THAT WILL BE ABLE TO CARRY THE |
| LOADS FOR THE 22'-0" SPAN. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING, |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS, MULLIONS |
| |
| 2) SHEET # 1 INDICATES IN THE NOTES THE INSTALATION OF |
| EUROWALL FOLDING DOOR SYSTEM, NO PRODUCT APPROVAL WAS |
| SUBMITTED FOR THIS REVIEW. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING, |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 3) SHEET # 1 APPEARS TO BE A OUTSWING DOOR SYSTEM, |
| PLEASE PROVIDE WHERE THE PROPERTY LINE IS LOCATED SHOW |
| COMPLIANCE WITH : |
| 2010 FBC-B 202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| FEET IN HEIGHT. |
| ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| |
| 4) NOTE MOST OUTSWING DOOR SYSTEMS ARE NOT PART OF A |
| EGRESS SYSTEM, SINCE WHEN THE DOOR SYSTEM IS CLOSED THE |
| ENTRY DOOR IS A SWING DOOR, BUT THERE IS USUALLY A |
| BOTTOM TRACK, PLEASE PROVIDE DETAILS THAT WILL COMPLY |
| WITH 2010 FL ACCESSIBILITY CODE: |
| MANEUVERING CLEARANCES AT RECESSED DOORS AND GATES |
| 404.2.4.4 FLOOR OR GROUND SURFACE. FLOOR OR GROUND |
| SURFACE WITHIN REQUIRED MANEUVERING CLEARANCES SHALL |
| COMPLY WITH 302. CHANGES IN LEVEL ARE NOT PERMITTED. |
| EXCEPTIONS: |
| 1. SLOPES NOT STEEPER THAN 1:48 SHALL BE PERMITTED. |
| 2. CHANGES IN LEVEL AT THRESHOLDS COMPLYING WITH |
| 404.2.5 SHALL BE PERMITTED. |
| 404.2.5 THRESHOLDS. |
| THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 5) SHEET # 1 ALSO HAS A DETAIL OF NEW ACOUSTICAL |
| CEILING SYSTEM. THE PLANS INDICATE SEE MANUFACTURERS |
| INSTRUCTIONS FOR DETAILS. NO LITERATURE HAS BEEN |
| SUVMITTED. PLEASE PROVIDE CODE COMPLIANCE WITH 2010 |
| FBC-B: |
| 808.1 ACOUSTICAL CEILING SYSTEMS. |
| THE QUALITY, DESIGN, FABRICATION AND ERECTION OF METAL |
| SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANEL |
| CEILINGS IN BUILDINGS OR STRUCTURES SHALL CONFORM WITH |
| GENERALLY ACCEPTED ENGINEERING PRACTICE, THE PROVISIONS |
| OF THIS CHAPTER AND OTHER APPLICABLE REQUIREMENTS OF |
| THIS CODE. |
| |
| 808.1.1 MATERIALS AND INSTALLATION. |
| ACOUSTICAL MATERIALS COMPLYING WITH THE INTERIOR FINISH |
| REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS AND |
| APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH. |
| |
| 808.1.1.1 SUSPENDED ACOUSTICAL CEILINGS. |
| SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND |
| ASTM C 636. |
| |
| : WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |