2014-04-24 15:42:523114 TUXEDO AVENUE
 PERMIT #14040502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL STORAGE AND STORAGE ACTIVITIES SHALL COMPLY WITH
 THE FLORIDA FIRE PREVENTION CODE 2010 EDITION.
  
 PLEASE INDICATE THE HOURS OF OPERATION FOR THE
 RECYCLING FACILITY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 BUILDING SKETCH #2 INDICATES TWO STORAGE AREAS AND A
 CLOSET; HOWEVER, THE OTHER 50% OF THE FLOOR SPACE IS
 NOT DESIGNATED WITH A USE.
  
 ALL EXISTING EXIT DOORS SHALL BE PROVIDED WITH
 ILLUMINATED EXIT SIGNS.
  
 BUILDING #5 NARRATIVE INDICATES A PROPOSED STORAGE
 HEIGHT OF LESS THAN 15 FEET. THE FIRE CODE REQUIRES
 HIGH-PILED STORAGE (12 FEET OR HIGHER) OF 2,500 SQ.FT.
 OR MORE TO BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  