2014-05-02 18:00:22 | BUILDING PLAN REVIEW |
| PERMIT: 14040502 |
| ADD: 3114 TUXEDO AVE. |
| CONT: TBD |
| TEL: (561)799-3700 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. MAY 02/ 2014 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE CHANGE OF |
| OCCUPANCY, IT IS MORE A CHANGE OF USE AND MATERIALS. |
| THE HANDLING OF THEM AND STORING THEM AS WELL. |
| |
| THE TYPES OF MATERIALS THAT YOUR FIRM WILL BE STORING |
| AND PROCESSING IS VARIOUS METALS. FORKLIFTS WILL BE |
| USED IN MOVING TTHE METALS AROUND THE SITE. WHAT TYPE |
| OF FUEL DOES THE FORK LIFTS USE? IF GASOLINE WHAT TPE |
| OF STORAGE CONTAINMENT IS USED TO CREATE CONTROL AREA. |
| 2010 FBC-B TABLE 307.1(2) |
| MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF |
| HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD |
| WILL ALLOW 30 GALLONS OF GASOLINE TO BE STORED IN |
| APPROVED CONTAINERS AND NOT BE CONSIDERED A HAZORDOUS |
| OCCUPANCY. |
| FOOTNOTE (B) .THE AGGREGATE QUANTITY IN USE AND STORAGE |
| SHALL NOT EXCEED THE QUANTITY LISTED FOR STORAGE |
| FOOTNOTE (P.) THE FOLLOWING SHALL NOT BE INCLUDED IN |
| DETERMINING THE MAXIMUM ALLOWABLE QUANTITIES: |
| 1. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON VEHICLES. |
| 2. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON MOTORIZED |
| EQUIPMENT OPERATED IN ACCORDANCE WITH THIS CODE. |
| 3. GASEOUS FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES |
| REGULATED BY THE FLORIDA BUILDING CODE, FUEL GAS. |
| 4. LIQUID FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES |
| REGULATED BY THE FLORIDA BUILDING CODE, MECHANICAL. |
| FOOTNOTE (M) FOR GALLONS OF LIQUIDS, DIVIDE THE AMOUNT |
| IN POUNDS BY 10 IN ACCORDANCE WITH THE FLORIDA FIRE |
| PREVENTION CODE |
| FOOTNOTE (F) . MAXIMUM ALLOWABLE QUANTITIES SHALL BE |
| INCREASED 100 PERCENT WHEN STORED IN APPROVED STORAGE |
| CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES AS |
| SPECIFIED IN THE FLORIDA FIRE PREVENTION CODE. WHERE |
| NOTE E ALSO APPLIES, THE INCREASE FOR BOTH NOTES SHALL |
| BE APPLIED ACCUMULATIVELY. |
| |
| 2) WILL THERE BE CUTTING OF ALLUMINUM AND MAGNESIUM? |
| 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |