2014-05-02 18:00:22BUILDING PLAN REVIEW
 PERMIT: 14040502
 ADD: 3114 TUXEDO AVE.
 CONT: TBD
 TEL: (561)799-3700
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 02/ 2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE CHANGE OF
 OCCUPANCY, IT IS MORE A CHANGE OF USE AND MATERIALS.
 THE HANDLING OF THEM AND STORING THEM AS WELL.
  
 THE TYPES OF MATERIALS THAT YOUR FIRM WILL BE STORING
 AND PROCESSING IS VARIOUS METALS. FORKLIFTS WILL BE
 USED IN MOVING TTHE METALS AROUND THE SITE. WHAT TYPE
 OF FUEL DOES THE FORK LIFTS USE? IF GASOLINE WHAT TPE
 OF STORAGE CONTAINMENT IS USED TO CREATE CONTROL AREA.
 2010 FBC-B TABLE 307.1(2)
 MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF
 HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD
 WILL ALLOW 30 GALLONS OF GASOLINE TO BE STORED IN
 APPROVED CONTAINERS AND NOT BE CONSIDERED A HAZORDOUS
 OCCUPANCY.
 FOOTNOTE (B) .THE AGGREGATE QUANTITY IN USE AND STORAGE
 SHALL NOT EXCEED THE QUANTITY LISTED FOR STORAGE
 FOOTNOTE (P.) THE FOLLOWING SHALL NOT BE INCLUDED IN
 DETERMINING THE MAXIMUM ALLOWABLE QUANTITIES:
 1. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON VEHICLES.
 2. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON MOTORIZED
 EQUIPMENT OPERATED IN ACCORDANCE WITH THIS CODE.
 3. GASEOUS FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES
 REGULATED BY THE FLORIDA BUILDING CODE, FUEL GAS.
 4. LIQUID FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES
 REGULATED BY THE FLORIDA BUILDING CODE, MECHANICAL.
 FOOTNOTE (M) FOR GALLONS OF LIQUIDS, DIVIDE THE AMOUNT
 IN POUNDS BY 10 IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE
 FOOTNOTE (F) . MAXIMUM ALLOWABLE QUANTITIES SHALL BE
 INCREASED 100 PERCENT WHEN STORED IN APPROVED STORAGE
 CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES AS
 SPECIFIED IN THE FLORIDA FIRE PREVENTION CODE. WHERE
 NOTE E ALSO APPLIES, THE INCREASE FOR BOTH NOTES SHALL
 BE APPLIED ACCUMULATIVELY.
  
 2) WILL THERE BE CUTTING OF ALLUMINUM AND MAGNESIUM?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  