Plan Review Notes
Plan Review Notes For Permit 14040466
Permit Number 14040466
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-21 14:20:32THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS:
  
 A REVIEW OF THE REMODELED SPACE AND THE LARGER ADJACENT
 SPACE SHALL BE DONE FOR SPRINKLER HEAD COVERAGE.
  
 ALL LIFE SAFETY SYSTEMS SHALL REMAIN FULLY OPERATIONAL
 DURING CONSTRUCTION.
  
 ALL WORK ON THE FIRE ALARM AND SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  