2014-07-15 14:02:34 | RESIDENTIAL (R3) ALTERATIONS, BUILDING REVIEW SECOND |
| CHECKLIST. |
| CODE: 2010 FBC. |
| |
| |
| 1- ALL DRAWINGS NEED TO HAVE THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| |
| **** RESPONSE TO INFORMATION SUBMITTED. |
| NOT ALL DRAWINGS HAVE THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. RESUBMIT ALL |
| DRAWINGS WITH THE DESIGNER'S NAME AND SIGNATURE. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED |
| FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY |
| REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL. |
| UNABLE TO VERIFY IF IT WAS APPROVED OR NOT. |
| |
| ****RESPONSE TO INFORMATION SUBMITTED: |
| |
| REPORT NO 2031 SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT |
| APPROVAL NUMBER. ALL THE FLORIDA PRODUCT APPROVALS HAVE |
| A NUMBER. THIS REPORT NEEDS NEEDS THE FLORIDA PRODUCT |
| APPROVAL NUMBER IN ORDER TO VERIFY STATUS. PROVIDE THE |
| FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO |
| THIS DOOR REPORT. IF THERE IS NOT FLORIDA PRODUCT |
| APPROVAL NUMBER, THEN, DOOR MANUFACTURER MAY APPLY FOR |
| LOCAL PRODUCT APPROVAL BY SUBMITTING ALL THE REQUIRED |
| DOCUMENTATION TO THE LOCAL BUILDING OFFICIAL FOR |
| APPROVAL. |
| |
| 3- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED: |
| A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS |
| REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING |
| BUILDING. |
| |
| **** RESPONSE TO INFORMATION SUBMITTED: |
| THERE IS NOT INFORMATION GIVEN ON THE TYPE AND SIZE OF |
| THE EXISTING BEDROOM WINDOW #2. IT ONLY GIVES THE SIZE |
| AND TYPE OF THE PROPOSED WINDOW. UNABLE TO VERIFY |
| COMPLIANCE WITH THE BEDROOM EGRESS REQUIREMENTS OF SEC. |
| 604.1 OF 2010 FBC-EXISTING BUILDING. IN ADDITION, |
| CLARIFY WHY WINDOW SCHEDULE SHOWS WINDOW #1 AS "IMPACT |
| EGRESS". WINDOW #1 IS LOCATED IN THE LIVING ROOM AND IS |
| NOT REQUIRED TO HAVE EGRESS WINDOWS. IS THE IMPACT |
| EGRESS WINDOW MEANT TO BE THE ONE IN THE BEDROOM?. |
| REVISE WINDOW SCHEDULE AS REQUIRED. |
| |
| *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |