2014-05-28 17:49:08 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 2- ROOF BUILT UP: |
| PROVIDE SIGNED AND SEALED STRUCTURAL EVALUATION BY |
| DESIGN PROFESSIONAL AS REQUIRED BY SEC. 506.2.2.1 OF |
| 2010 FBC-EXISTING BUILDING. DESIGN PROFESSIONAL TO |
| PROVIDE STRUCTURAL ANALYSIS SHOWING THAT PROPOSED |
| STRUCTURAL MEMBERS AND CONNECTORS SPECIFIED ON PLANS |
| SUBMITTED WILL MEET THE LATERAL AND UPLIFT LOADS |
| REQUIRED BY SEC. R301 OF 2010 FBC. |
| |
| 3- DESIGN PROFESSIONAL TO REVISE INFORMATION ON SHEET |
| 6.0 |
| A) REVISE THE ROOF ZONES ON THE GABLE ROOF PLAN. THE |
| WHOLE GABLE END FOR A MINIMUM DISTANCE OF 5'-0" IS |
| CONSIDERED ROOF ZONE #3. SEE FIGURE R803.2.3.1 OF 2010 |
| FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| |
| B) REVISE THE DESIGN CRITERIA: CURRENT ASCE EDITION |
| THAT CORRESPONDS TO FBC 2010 IS ASCE 7-10 NOT ASCE |
| 7-05. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| PROFIT AND DESIGN PROFESSIONAL FEES. UPDATE THE |
| VALUATION AS REQUIRED TO INCLUDE THE ROOF BUILT UP, |
| REPLACEMENT OF DOOR AND WINDOWS, DESIGN PROFESSIONAL |
| FEES. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. (NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR). |
| |
| B) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED |
| FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY |
| REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL. |
| UNABLE TO VERIFY IF IT WAS APPROVED OR NOT. |
| |
| 6- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED: |
| A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS |
| REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING |
| BUILDING. |
| |
| B) SHEET 4.0: CURRENT ASCE EDITION THAT CORRESPONDS TO |
| FBC-2010 IS ASCE 7-10 NOT ASCE 7-05. REVISE AS |
| REQUIRED. |
| |
| *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |