Plan Review Notes
Plan Review Notes For Permit 14040460
Permit Number 14040460
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-28 17:49:08RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- ROOF BUILT UP:
 PROVIDE SIGNED AND SEALED STRUCTURAL EVALUATION BY
 DESIGN PROFESSIONAL AS REQUIRED BY SEC. 506.2.2.1 OF
 2010 FBC-EXISTING BUILDING. DESIGN PROFESSIONAL TO
 PROVIDE STRUCTURAL ANALYSIS SHOWING THAT PROPOSED
 STRUCTURAL MEMBERS AND CONNECTORS SPECIFIED ON PLANS
 SUBMITTED WILL MEET THE LATERAL AND UPLIFT LOADS
 REQUIRED BY SEC. R301 OF 2010 FBC.
  
 3- DESIGN PROFESSIONAL TO REVISE INFORMATION ON SHEET
 6.0
 A) REVISE THE ROOF ZONES ON THE GABLE ROOF PLAN. THE
 WHOLE GABLE END FOR A MINIMUM DISTANCE OF 5'-0" IS
 CONSIDERED ROOF ZONE #3. SEE FIGURE R803.2.3.1 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 B) REVISE THE DESIGN CRITERIA: CURRENT ASCE EDITION
 THAT CORRESPONDS TO FBC 2010 IS ASCE 7-10 NOT ASCE
 7-05.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES. UPDATE THE
 VALUATION AS REQUIRED TO INCLUDE THE ROOF BUILT UP,
 REPLACEMENT OF DOOR AND WINDOWS, DESIGN PROFESSIONAL
 FEES.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. (NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR).
  
 B) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED
 FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY
 REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL.
 UNABLE TO VERIFY IF IT WAS APPROVED OR NOT.
  
 6- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING.
  
 B) SHEET 4.0: CURRENT ASCE EDITION THAT CORRESPONDS TO
 FBC-2010 IS ASCE 7-10 NOT ASCE 7-05. REVISE AS
 REQUIRED.
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
  