Plan Review Notes For Permit 14040384 |
Permit Number |
14040384 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-10 12:10:13 | LOAD CALCULATION IS INCOMPLETE. RISER DIAGRAM IS | | LACKING WIRE SIZES. FBC 107.3.5.1.2 ELECTRICAL | | 1. ELECTRICAL: | | WIRING | | SERVICES | | FEEDERS AND BRANCH CIRCUITS | | OVERCURRENT PROTECTION | | GROUNDING | | WIRING METHODS AND MATERIALS | | | | FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN | | REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS | | EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. | | I CAN BE AT 561-805-6717 OR AT [email protected] | | | | PUT APPLICATION IN DENIED DRAWER UNDER SMALL F. DAH | | |
|