Plan Review Notes For Permit 14040381
Permit Number 14040381
Review Stop B
Sequence Number 2
Notes
Date Text
2014-04-21 13:50:18RESIDENTIAL (R3) REROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF (DCA RULE 9N-3):
 A) NOA 13-0204.03 APPROVED ASSEMBLY SUBMITTED REQUIRES
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL. PROVIDE 2 SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
 B) NOA 13-0204.03 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. PROVIDE 2
 COPIES.
  
 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT. (2 COPIES).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712