2014-04-14 10:37:32RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF:
 A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3. NONE SUBMITTED AT THIS TIME.
  
 B) ON PRODUCT APPROVAL CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 C) IF FLAT ROOF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED AS
 REQUIRED BY THE PRODUCT APPROVAL SUBMITTED.
  
 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT. (2 COPIES). DCA RULE 9N-3.
  