2014-06-24 08:50:06 | PLUMBING PLAN REVIEW |
| PERMIT: 14040379 |
| ADD: 2101 OKEECHOBEE BLVD |
| CONT: HEDRICK BROTHERS RENE YERNANDEZ CELL 561-568-4182 |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2ND REVIEW |
| DATE: TUES. JUNE 24/ 2014 |
| ACTION: PROVISO |
| |
| 1) A SEPARATE PERMIT IS REQUIRED FOR THE OIL SEPARATOR |
| FOR TRACKING PURPOSES. SHEET P0.2 INDICATES THE |
| PROPOSED USE OF A: |
| SCHIER OIL/ SAND SEPARATOR OS-100 |
| |
| 2) DEFERRED SUBMITTALS: |
| SHEET P.01 DOES NOT LIST THE CAR WASH FLOOR DRAIN NOR |
| IS THE INFORMATION FOUND ON P2.1.3. |
| 2010 FBC-P 412.1 APPROVAL. |
| FLOOR DRAINS SHALL CONFORM TO ASME A112.3.1, ASME |
| A112.6.3 OR CSA B79. TRENCH DRAINS SHALL COMPLY WITH |
| ASME A112.6.3. |
| |
| 412.2 FLOOR DRAINS. |
| FLOOR DRAINS SHALL HAVE REMOVABLE STRAINERS. THE FLOOR |
| DRAIN SHALL BE CONSTRUCTED SO THAT THE DRAIN IS CAPABLE |
| OF BEING CLEANED. ACCESS SHALL BE PROVIDED TO THE DRAIN |
| INLET. READY ACCESS SHALL BE PROVIDED TO FLOOR DRAINS. |
| RESPONSE: SEE ATTACHED BROADWAY EQUIPMENT PLANS |
| PROVIDED BY OTHERS. NOT PART OF PACKAGE. |
| |
| 3 )DEFERRED SUBMITTALS: |
| SHEET P2.1.3. THE PLANS REFERENCE BROADWAY EQUIPMENT |
| CO. BUT NO FURTHER DIRECTION IS GIVEN WHERE TO FIND |
| DETAILS ON THE TRENCH DRAIN, NEITHER THE STRUCTURAL |
| PLANS PROVIDE ANY INFORMATION. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| RESPONSE: SEE ATTACHED BROADWAY EQUIPMENT PLANS |
| PROVIDED BY OTHERS. NOT PART OF PACKAGE. |
| |
| |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |