2014-04-25 13:19:29 | PLUMBING PLAN REVIEW |
| PERMIT: 14040379 |
| ADD: 2101 OKEECHOBEE BLVD |
| CONT: HEDRICK BROTHERS RENE YERNANDEZ CELL 561-568-4182 |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: FRIDAY/ APRIL 25/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET P.01 DOES NOT LIST THE CAR WASH FLOOR DRAIN |
| NOR IS THE INFORMATION FOUND ON P2.1.3. |
| 2010 FBC-P 412.1 APPROVAL. |
| FLOOR DRAINS SHALL CONFORM TO ASME A112.3.1, ASME |
| A112.6.3 OR CSA B79. TRENCH DRAINS SHALL COMPLY WITH |
| ASME A112.6.3. |
| |
| 412.2 FLOOR DRAINS. |
| FLOOR DRAINS SHALL HAVE REMOVEABLE STRAINERS. THE FLOOR |
| DRAIN SHALL BE CONSTRUCTED SO THAT THE DRAIN IS CAPABLE |
| OF BEING CLEANED. ACCESS SHALL BE PROVIDED TO THE DRAIN |
| INLET. READY ACCESS SHALL BE PROVIDED TO FLOOR DRAINS. |
| |
| 2) SHEET P.02 DETAIL FOR ROOF PIPING SUPPORT, TAN PRO |
| 801 IS INDICATED TO HAVE MIAMI DADE PRODUCT TEST |
| REPORT, PLEASE PROVIDE REPORT SHOWING COMPLIANCE WITH |
| 2010 FBC-P 308.4 STRUCTURAL ATTACHMENT. |
| HANGERS AND ANCHORS SHALL BE ATTACHED TO THE BUILDING |
| CONSTRUCTION IN AN APPROVED MANNER. |
| 308.5 INTERVAL OF SUPPORT. PIPE SHALL BE SUPPORTED IN |
| ACCORDANCE WITH TABLE 308.5. |
| |
| 3) WITHIN THE PERMIT SET OF PLANS THERE ARE NO CIVIL |
| PLANS OR OVER ALL SITE BUILDING SEWER PLANS PROVIDING A |
| OVER ALL LAYOUT OF THE VARIOUS BUILDING SEWERS AND HOW |
| THEY DEVELOP INTO THE BUILDING SEWER PLAN. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5.1.3(4) |
| BUILDING SEWER, MINIMUM REQUIREMENTS FOR COMMERCIAL |
| PLUMBING PLAN REVIEW. |
| |
| 4) SHEET P2.1.2: |
| 4A) THE PLANS SHOW CAR LIFTS BUT THERE IS NO MENTION AS |
| TO WHAT TYPE SYSTEM THESE LIFTS ARE, IF THEY ARE |
| HYDROLIC, ELECTRIC, PLEASE PROVIDE THE MANUFACTURERS |
| SPECIFICATIONS AND INSTALATION INFORMATION. CONCERNS |
| WITH HYDROLIC FLUID LEAKS AND CLEAN UP OF SUCH LEAKS. |
| THE SAME ISSUE |
| IS WITH THE PARTS DELIVERY LIFT TO THE MEZANINE LEVEL, |
| THE STRUCTURAL SHEETS SHOW A RECESS INTHE SLAB. |
| HYDROLIC LIFTS MAY NEED TO COMPLY WITH 1003.4 OIL |
| SEPARATORS OR A OIL SEPARATOR IS NOT REQUIRED IN |
| HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| IS INSTALLED (EXCEPTION). |
| |
| 4B) THIS OCCUPANCY BEING A AUTOMOBILE REPAIR & SERVICE |
| GARAGE WILL NEED TO SHOW COMPLIANCE WITH 2010 FBC-P |
| 1003.4.2.2 GARAGES AND SERVICE STATIONS. |
| WHERE AUTOMOBILES ARE SERVICED, GREASED, REPAIRED OR |
| WASHED OR WHERE GASOLINE IS DISPENSED, OIL SEPARATORS |
| SHALL HAVE A MINIMUM CAPACITY OF 6 CUBIC FEET (0.168 |
| M3) FOR THE FIRST 100 SQUARE FEET (9.3 M2) OF AREA TO |
| BE DRAINED, PLUS 1 CUBIC FOOT (0.28 M3) FOR EACH |
| ADDITIONAL 100 SQUARE FEET (9.3 M2) OF AREA TO BE |
| DRAINED INTO THE SEPARATOR. PARKING GARAGES IN WHICH |
| SERVICING, REPAIRING OR WASHING IS NOT CONDUCTED, AND |
| IN WHICH GASOLINE IS NOT DISPENSED, SHALL NOT REQUIRE A |
| SEPARATOR. AREAS OF COMMERCIAL GARAGES UTILIZED ONLY |
| FOR STORAGE OF AUTOMOBILES ARE NOT REQUIRED TO BE |
| DRAINED THROUGH A SEPARATOR. |
| |
| 5) SHEET P2.1.3. |
| 5A) THE PLANS REFERENCE BROADWAY EQUIPMENT CO. BUT NO |
| FURTHER DIRECTION IS GIVEN WHERE TO FIND DETAILS ON THE |
| TRENCH DRAIN, NEITHER THE STRUCTURAL PLANS PROVIDE ANY |
| INFORMATION. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 5B) PLEASE PROVIDE A DOMESTIC WATER PLAN FOR THIS |
| BUILDING SHOW HOW THE POTABLE WATER WILL BE HOOKED INTO |
| THE CAR WASH RECLAIMED WATER SYSTEM AND PROTECTION OF |
| THE POTABLE WATER, 2010 FBC-P 608.3 608.3 DEVICES, |
| APPURTENANCES, APPLIANCES AND APPARATUS. |
| ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS |
| INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS |
| STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR |
| STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER |
| SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION |
| AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY |
| SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS, |
| COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER |
| APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE |
| WATER SHALL BE PROTECTED AGAINST CONTAMINATION. |
| |
| 5C) THE PLANS APEAR TO HAVE THE VENT FOR THE OIL |
| SEPARATOR BUT THERE IS NO VENT SHOWN FOR THE FLOW |
| CONTROL DEVICE (AIR INTAKE) 2010 FBC-P 1003.3.4.2. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |