2014-08-18 11:33:03BUILDING PLAN REVIEW
 SUBMITTAL: 14040366
 PERMIT: 14040366
 ADD: 700 S ROSEMARY
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 18/ 2014
 ACTION: DENIED
  
 1) THIS REVISION CAME IN FOR ORIGINALLY PAVER WALKWAY,
 ASPHALT AND STIPPING REVISION TO THE PERMIT. WITHIN
 THIS SUBMITTAL IS SIGHT LIGHTING FOR THE WALKWAY. THE
 SITE PLAN NOR THE ELECTICAL PLANS PROVIDE AT WHAT
 HEIGHT THE FIXTURES WILL BE INSTALLED. THE
 MANUFACTURERS SPECIFICATION FOR THE COLUMIA LIGHTING
 FIXTURE A OUTDOOR SIGN AND FACADE LUMINAIRE SHEET 2
 INDICATES THESE FIXTURES CAN BE MOUNTED FORM 3'-3" TO
 5'-0" AWAY FROM THE WALL. THE CONCERN IS COMPLIANCE
 WITH THE 2010 FBC-ACCESSIBILITY CODE 307.2. PROTRUDING
 OBJECTS.
  
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER