Plan Review Notes For Permit 14040277
Permit Number 14040277
Review Stop ENG
Sequence Number 1
Notes
Date Text
2014-05-02 11:07:34#1 WATERLINE ON-SITE WILL BE CONSIDERED PRIVATE. SHEET
 C-5 WILL NEED REVISION SHOWING FIRE AND DOMESTIC
 SERVICE WITH SEPARATE TAPS. FIRE LOOP WILL REQUIRE DCDA
 AT EACH CITY CONNECTION NEAR RPOERTYLINE.
  
 #2 WATERLINE EASEMENT ON-SITE WILL NOT BE REQUIRED.
  