2014-04-24 09:58:06ADDRESS: 1750 N. CONGRESS WPB
 PERMIT#: 14040245
 1ST ELECTRICAL REVIEW
 ACTION: DENIED.
 CODE: 2008 NEC AND 2010 FBC
  
 DEFICIENCIES
  
 907.1.2 FIRE ALARM SHOP DRAWINGS. [F]
 SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED
 FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION,
 AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE
 FOLLOWING:
 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS.
 2) LOCATIONS OF ALARM-INITIATING DEVICES.
 3) LOCATIONS OF ALARM NOTIFICATION APPLIANCES,
 INCLUDING CANDELA RATINGS FOR VISIBLE ALARM
 NOTIFICATION APPLIANCES.
 4) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS
 AND NOTIFICATION POWER SUPPLIES.
 5) ANNUNCIATORS.
 6) POWER CONNECTION.
 7) BATTERY CALCULATIONS.
 8) CONDUCTOR TYPE AND SIZES.
 9) VOLTAGE DROP CALCULATIONS.
 10) MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS
 AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND
 MATERIALS.
 11) DETAILS OF CEILING HEIGHT AND CONSTRUCTION.
 12) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.
 13) CLASSIFICATION OF THE SUPERVISING STATION.
  
 THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED:
 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS.
 2) LOCATIONS OF ALARM NOTIFICATION APPLIANCES,
 INCLUDING CANDELA RATINGS FOR VISIBLE ALARM
 NOTIFICATION APPLIANCES.
 3) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS
 AND NOTIFICATION POWER SUPPLIES.
 4) CONDUCTOR TYPE AND SIZES.
 5) DETAILS OF CEILING HEIGHT AND CONSTRUCTION.
 6) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.
 7) CLASSIFICATION OF THE SUPERVISING STATION.
  
 ADDITIONALLY
 FBC
 [F] 907.2.18.1 SMOKE DETECTORS. A MINIMUM OF ONE SMOKE
 DETECTOR LISTED FOR THE INTENDED PURPOSE SHALL BE
 INSTALLED IN THE FOLLOWING AREAS:
 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER,
 TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS.
 2) ELEVATOR LOBBIES.
 3) THE MAIN RETURN AND EXHAUST AIR PLENUM OF EACH
 AIR-CONDITIONING SYSTEM SERVING MORE THAN ONE STORY AND
 LOCATED IN A SERVICEABLE AREA DOWNSTREAM OF THE LAST
 DUCT INLET
 4) EACH CONNECTION TO A VERTICAL DUCT OR RISER SERVING
 TWO OR MORE FLOORS FROM AIR RETURN AIR DUCTS OR PLENUMS
 OF HEATING, VENTILATING SYSTEM, EXCEPT THAT IN GROUP R
 OCCUPANCIES, A LISTED SMOKE DETECTOR IS ALLOWED TO BE
 USED IN EACH AIR RISER CARRYING NOT MORE THAN 5000 CFM
 (2.4 M3/S) AND SERVING NOT MORE THAN 10 AIR INLET
 OPENINGS.
  
 THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED:
 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER,
 TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS,
 A LISTED SMOKE DETECTOR SHALL BE INSTALLED.
 2) THE ELECTRICAL ROOM IS NOTED BUT NO SMOKE DETECTOR
 IS SHOWN.
 .
  
 FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN
 REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS
 EXAMINER, PX3421. I CAN BE AT 561-805-6717 OR AT
 [email protected]
  