2014-04-24 09:58:06 | ADDRESS: 1750 N. CONGRESS WPB |
| PERMIT#: 14040245 |
| 1ST ELECTRICAL REVIEW |
| ACTION: DENIED. |
| CODE: 2008 NEC AND 2010 FBC |
| |
| DEFICIENCIES |
| |
| 907.1.2 FIRE ALARM SHOP DRAWINGS. [F] |
| SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED |
| FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION, |
| AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE |
| FOLLOWING: |
| 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. |
| 2) LOCATIONS OF ALARM-INITIATING DEVICES. |
| 3) LOCATIONS OF ALARM NOTIFICATION APPLIANCES, |
| INCLUDING CANDELA RATINGS FOR VISIBLE ALARM |
| NOTIFICATION APPLIANCES. |
| 4) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS |
| AND NOTIFICATION POWER SUPPLIES. |
| 5) ANNUNCIATORS. |
| 6) POWER CONNECTION. |
| 7) BATTERY CALCULATIONS. |
| 8) CONDUCTOR TYPE AND SIZES. |
| 9) VOLTAGE DROP CALCULATIONS. |
| 10) MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS |
| AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND |
| MATERIALS. |
| 11) DETAILS OF CEILING HEIGHT AND CONSTRUCTION. |
| 12) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. |
| 13) CLASSIFICATION OF THE SUPERVISING STATION. |
| |
| THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED: |
| 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. |
| 2) LOCATIONS OF ALARM NOTIFICATION APPLIANCES, |
| INCLUDING CANDELA RATINGS FOR VISIBLE ALARM |
| NOTIFICATION APPLIANCES. |
| 3) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS |
| AND NOTIFICATION POWER SUPPLIES. |
| 4) CONDUCTOR TYPE AND SIZES. |
| 5) DETAILS OF CEILING HEIGHT AND CONSTRUCTION. |
| 6) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. |
| 7) CLASSIFICATION OF THE SUPERVISING STATION. |
| |
| ADDITIONALLY |
| FBC |
| [F] 907.2.18.1 SMOKE DETECTORS. A MINIMUM OF ONE SMOKE |
| DETECTOR LISTED FOR THE INTENDED PURPOSE SHALL BE |
| INSTALLED IN THE FOLLOWING AREAS: |
| 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS. |
| 2) ELEVATOR LOBBIES. |
| 3) THE MAIN RETURN AND EXHAUST AIR PLENUM OF EACH |
| AIR-CONDITIONING SYSTEM SERVING MORE THAN ONE STORY AND |
| LOCATED IN A SERVICEABLE AREA DOWNSTREAM OF THE LAST |
| DUCT INLET |
| 4) EACH CONNECTION TO A VERTICAL DUCT OR RISER SERVING |
| TWO OR MORE FLOORS FROM AIR RETURN AIR DUCTS OR PLENUMS |
| OF HEATING, VENTILATING SYSTEM, EXCEPT THAT IN GROUP R |
| OCCUPANCIES, A LISTED SMOKE DETECTOR IS ALLOWED TO BE |
| USED IN EACH AIR RISER CARRYING NOT MORE THAN 5000 CFM |
| (2.4 M3/S) AND SERVING NOT MORE THAN 10 AIR INLET |
| OPENINGS. |
| |
| THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED: |
| 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS, |
| A LISTED SMOKE DETECTOR SHALL BE INSTALLED. |
| 2) THE ELECTRICAL ROOM IS NOTED BUT NO SMOKE DETECTOR |
| IS SHOWN. |
| . |
| |
| FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN |
| REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS |
| EXAMINER, PX3421. I CAN BE AT 561-805-6717 OR AT |
| [email protected] |
| |