Plan Review Notes
Plan Review Notes For Permit 14040237
Permit Number 14040237
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-22 15:22:31114 SOUTH OLIVE AVENUE
 PERMIT #14040237
 MASTER #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE FIRE PROTECTION ENGINEERING CONSTRUCTION DOCUMENTS
 ESTABLISH "J.F. SHANNON" AS THE ENGINEER OF RECORD;
 THEREFORE, THE FIRE SPRINKLER SHOP DRAWINGS SHALL NOT
 BE SEALED BY ANOTHER ENGINEER UNLESS MR. LAWRENCE
 BORAIKO (ENGINEER) IS DESIGNATED AS THE "DELEGATED
 ENGINEER" BY THE ENGINEER OF RECORD.
  
 PER FLORIDA BUILDING CODE SECTION 905.3.1 A CLASS I
 STANDPIPE SYSTEM IS REQUIRED THROUGHOUT BUILDINGS WHERE
 THE FLOOR LEVEL OF THE HIGHEST STORY IS LOCATED MORE
 THAN 30 FEET ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS.
  
 BACKFLOW PREVENTER LOCATION ISSUE: PER NFPA 24 SECTION
 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 ***NOTE: A SEPARATE PERMIT IS NEEDED FOR THE
 UNDERGROUND FIRE LINE TAP***
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  