Plan Review Notes
Plan Review Notes For Permit 14040234
Permit Number 14040234
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-08 19:01:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND
 SPEED WITH EXPOSURE CATEGORY C. THE MAXIMUM DESIGN
 PRESSURE FOR THE CERTAIN TEED MODIFIED ROOFING OVER
 WOOD DECKS IS -52.5 PSF. THIS WILL NOT MEET THE
 REQUIRED PRESSURES. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 OF NOA
 NO.13-0204.03. FBC 1609.1
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING. FBC
 1609.1
  
 3) A FLORIDA COVER SHEET FOR FL# 2533-R8 WAS ATTACHED
 TO NOA NO.13-0204.04 FOR THE CERTAIN-TEED MODIFIED
 ROOFING OVER CONCRETE DECKS. THE NOA IS NOT THE
 INSTALLATION INSTRUCTIONS FOR THIS FLORIDA PRODUCT
 APPROVAL. THEY ARE TWO SEPARATE PRODUCT APPROVALS. IF
 YOU WANT TO USE THE FLORIDA PRODUCT APPROVAL SUBMIT THE
 CURRENT REVISION OF IT (R-10) WITH THE PROPER
 INSTALLATION INSTRUCTIONS. THE MIAMI-DADE NOA IS
 ACCEPTABLE AS IT IS WITHOUT THE FL COVERSHEET. PLEASE
 CLARIFY. DCA RULE 9N-3 AND CITY AMENDMENTS 107.2.1
  
  
 4) A FLORIDA PRODUCT APPROVAL ( FL16709 ) FOR
 CERTAIN-TEED MODIFIED ROOFING WAS SUBMITTED. IF YOU
 WISH TO USE THIS PRODUCT APPROVAL, YOU ARE REQUIRED TO
 MARK THE SYSTEM THAT YOU WILL USE AND ALL THE
 APPROPRIATE FASTENING OPTIONS ON THE INSTALLATION
 INSTRUCTIONS. SUBMIT TWO COPIES OF A ROOF DIAGRAM THAT
 WILL CLARIFY WHERE THIS WILL BE INSTALLED AND WHERE THE
 OTHER SYSTEMS WILL BE INSTALLED. CITY AMENDMENTS
 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]