2014-04-08 19:01:49 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND |
| SPEED WITH EXPOSURE CATEGORY C. THE MAXIMUM DESIGN |
| PRESSURE FOR THE CERTAIN TEED MODIFIED ROOFING OVER |
| WOOD DECKS IS -52.5 PSF. THIS WILL NOT MEET THE |
| REQUIRED PRESSURES. SUBMIT SIGNED AND SEALED RAS 117 |
| CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 OF NOA |
| NO.13-0204.03. FBC 1609.1 |
| |
| 2) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING. FBC |
| 1609.1 |
| |
| 3) A FLORIDA COVER SHEET FOR FL# 2533-R8 WAS ATTACHED |
| TO NOA NO.13-0204.04 FOR THE CERTAIN-TEED MODIFIED |
| ROOFING OVER CONCRETE DECKS. THE NOA IS NOT THE |
| INSTALLATION INSTRUCTIONS FOR THIS FLORIDA PRODUCT |
| APPROVAL. THEY ARE TWO SEPARATE PRODUCT APPROVALS. IF |
| YOU WANT TO USE THE FLORIDA PRODUCT APPROVAL SUBMIT THE |
| CURRENT REVISION OF IT (R-10) WITH THE PROPER |
| INSTALLATION INSTRUCTIONS. THE MIAMI-DADE NOA IS |
| ACCEPTABLE AS IT IS WITHOUT THE FL COVERSHEET. PLEASE |
| CLARIFY. DCA RULE 9N-3 AND CITY AMENDMENTS 107.2.1 |
| |
| |
| 4) A FLORIDA PRODUCT APPROVAL ( FL16709 ) FOR |
| CERTAIN-TEED MODIFIED ROOFING WAS SUBMITTED. IF YOU |
| WISH TO USE THIS PRODUCT APPROVAL, YOU ARE REQUIRED TO |
| MARK THE SYSTEM THAT YOU WILL USE AND ALL THE |
| APPROPRIATE FASTENING OPTIONS ON THE INSTALLATION |
| INSTRUCTIONS. SUBMIT TWO COPIES OF A ROOF DIAGRAM THAT |
| WILL CLARIFY WHERE THIS WILL BE INSTALLED AND WHERE THE |
| OTHER SYSTEMS WILL BE INSTALLED. CITY AMENDMENTS |
| 107.2.1 |
| |