2015-01-29 17:46:45 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| COMMENT FROM PREVIOUS REVIEWS, EITHER NOT ADDRESSED, |
| PARTIALLY ADDRESSED, OR ADDRESSED INCORRECTLY: |
| |
| 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE |
| VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND |
| IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED, FBC |
| 1609. |
| |
| ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING, |
| SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A |
| REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP |
| DRAWING REVIEW STAMP, OR BY LETTER. |
| |
| THE ENGINEERING PROVIDED BY MOLNAR JORDAN & ASSOCIATES |
| SPECIFIED 6' EMBEDMENT IN REVIEW #3, ENGINEERING BY |
| CHRIS ARLANDSON SPECIFIED 7' EMBEDMENT (WHICH IS NO |
| LONGER IN THE PACKAGE), AND THE ENGINEERING BY MOLNAR |
| JORDAY & ASSOCIATES HAS NOW BEEN REVISED TO 7'. THIS |
| WOULD BE ACCEPTABLE EXCEPT THAT THE 7' EMBEDMENT |
| STRUCTURAL ENGINEERING (CHRIS ARLANDSON, PE) IS NO |
| LONGER A PART OF THIS SUBMITTAL (OR THE ISSUED |
| SUBMITTAL). |
| |
| NEW CALCULATIONS WERE SUBMITTED (PREPARED BY BRIAN J. |
| SIELAFF, PE AND TAMARACK GROVE ENGINEERING) WHICH |
| REQUIRE AN 8'6" EMBEDMENT (SEE PAGE 7 OF 9). PLEASE |
| CORRELATE. A CERTIFICATE OF AUTHORIZATION (BUSINESS |
| LICENSE) FOR THE ENGINEERING COMPANY "TAMARACK GROVE |
| ENGINEERING" IS REQUIRED, AND THE LICENSE NUMBER IS TO |
| BE ON THE CALCULATIONS, FS471, FAC61G15-23.002. REVIEW |
| BY DESIGNER OF RECORD IS REQUIRED FOR DELEGATED |
| ENGINEERING. |
| |
| 2. VALUE HAS BEEN ADJUSTED PER CONTRACT, PLEASE PAY |
| FEES, THIS MAY BE DONE ONLINE, ON OUR AUTOMATED SYSTEM |
| BY FOLLOWING THE PROMPTS (561-805-6700), OR AT THE |
| BUILDING DIVISION CUSTOMER SERVICE COUNTER. |
| |
| 3. FIXTURE CALCS NOT PROVIDED. PROVIDE AT INSPECTION - |
| SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION FOR |
| THE FIXTURE CALCS MAY BE REQUIRED, FBC 107, FBC 1609. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |