2014-07-08 11:53:3904/04/14 OUT PER M. ALBARRAN
2014-04-14 15:19:24THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED
 DOCUMENTATION AND NOTES AS MENTIONED BELOW:
 1. YOU SHALL PROVIDE SPEC SHEETS FOR THE POLES AS WELL
 AS FOR THE PROPOSED HEADS.
 2. YOU SHALL PROVIDE ENGINEERED WIND LOAD CALCULATIONS
 OF THE POLES WITH THE RESPECTIVE HEADS ATTACHED.
 3. YOU SHALL COMPLY WITH ALL THE REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION REQUIREMENTS FOR EXTERIOR
 LIGHTING.
 4. IF YOU WILL BE USING EXISTING WIRING, YOU MUST
 VERIFY THAT IT COMPLIES WITH NEC 300.5(B).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT MIKE ALBARRAN (561) 805-6718
  
 ROUTED TO SMALL DENIED BIN "R"