2014-04-23 07:28:10 | BUILDING PLAN REVIEW |
| PERMIT: 14040157 |
| ADD: 1875 PALM BEACH LAKES SUITE # A05 |
| CONT: TBD |
| TEL: (561) 373-3902 KARI |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. APRIL 23/2014 |
| ACTION: DENIED |
| |
| 1) PB OUTLET MALLS: |
| A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| |
| 2) PLANS HAVE NOT BEEN STAMPED WITH THE APPROVED STAMP |
| FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLET SKYE |
| GROUP TENANT COORDINATION STAMP. |
| |
| 3) SHEET A01: |
| |
| 3A) PLEASE REVIEW THE OCCUPANT LOAD COUNT OF 910 |
| PERSONS VERSES THE EGRESS PERSON COUNT WHEN TOTALED OF |
| 747. DISCREPANCY. 910 PERSONS OCCUPANT LOAD COUNT TIMES |
| (X) 0.20= 182.0 INCHES. |
| |
| 3B) EGRESS WIDTH PER 2010 FBC-B SECTION 1005.1 MINIMUM |
| REQUIRED EGRESS WIDTH. |
| THE MEANS OF EGRESS WIDTH SHALL NOT BE LESS THAN |
| REQUIRED BY THIS SECTION. THE TOTAL WIDTH OF MEANS OF |
| EGRESS IN INCHES (MM) SHALL NOT BE LESS THAN THE TOTAL |
| OCCUPANT LOAD SERVED BY THE MEANS OF EGRESS MULTIPLIED |
| BY 0.3 INCH (7.62 MM) PER OCCUPANT FOR STAIRWAYS AND BY |
| 0.2 INCH (5.08 MM) PER OCCUPANT FOR OTHER EGRESS |
| COMPONENTS. THE WIDTH SHALL NOT BE LESS THAN SPECIFIED |
| ELSEWHERE IN THIS CODE. MULTIPLE MEANS OF EGRESS SHALL |
| BE SIZED SUCH THAT THE LOSS OF ANY ONE MEANS OF EGRESS |
| SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 |
| PERCENT OF THE REQUIRED CAPACITY. THE MAXIMUM CAPACITY |
| REQUIRED FROM ANY STORY OF A BUILDING SHALL BE |
| MAINTAINED TO THE TERMINATION OF THE MEANS OF EGRESS. |
| |
| 4) PLEASE SEE SHEET A1.2 WITH THE OCCUPANT LOAD OF 1080 |
| OCCUPANTS, TOTAL OCCUPANTS = 1000 VERSES THE OCCUPANT |
| LOAD OF 910 FOUND ON SHEET A01. PLEASE EXPLAIN WHICH OF |
| THE OCCUPANT LOADS IS CORRECT, NOTE IF THE 1000 OR MORE |
| IS CORRECT THE 2010 FBC-B TABLE 1021.1WOULD REQUIRE A |
| 4TH EXIT WHICH WOULD REQUIRE THE EXIT ACCESS THROUGH |
| THE STOCK/ STORAGE ROOM QND WOULD NEED TO MEET |
| THEFOLLOWING REQUIREMENTS: |
| 2010 FBC-B 014.2 EGRESS THROUGH INTERVENING SPACES. |
| EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| THIS SECTION. |
| 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE |
| ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H |
| OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS |
| TRAVEL TO AN EXIT. |
| EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H, |
| S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING |
| ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD |
| OCCUPANCY GROUP. |
| 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| EXCEPTIONS: |
| 1. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH A KITCHEN |
| AREA SERVING ADJOINING ROOMS CONSTITUTING PART OF THE |
| SAME DWELLING UNIT OR SLEEPING UNIT. |
| 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| FOLLOWING ARE MET: |
| 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| THAT FOUND IN THE MAIN RETAIL AREA; |
| 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| THROUGH THE STOCKROOM; |
| 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| EGRESS SIDE; AND |
| 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| TO THE EXIT WITHOUT OBSTRUCTIONS. |
| |
| 5) SHEET A2.3 SHOWS THE MEZZANINE AREA, 1ST AND 2ND |
| FLOOR, THE 2 HOUR FIRE RATED WALL ASSMBLY, BUT THE DOOR |
| LEADING FROM THE 2 HR WALL ASSEMBLY TO THE GENERAL |
| SALES FLOOR IS NOT IDENTIFIED. PLEASE REFER TO SHEET |
| A3.2 THE DOOR SCHEDULE AND REVIEW ALL THE DOORS 1ST AND |
| 2ND FLOOR ON THE DOOR SCHEDULE FOR THIS AREA THEY ARE |
| ALL WRONG. NO FIRE RATING FOUND FOR THIS DOOR. SHEET |
| A7.2 DOORS MATCH THE SCHEDULE BUT DOOR 123 DOES NOT |
| HAVE A 1 1/2 HR FIRE RATING. SEE OPENING PROTECTIVES |
| 2010 FBC-B TABLE 7.15 |
| |
| 6) THE PLANS ALSO SHOW A VERTICAL LIFT BUT NO PRODUCT |
| INFORMATION WAS PROVIDED ON THE LIFT. 2010 FL |
| ACCESSIBILITY CODE 221.1.1 FLORIDA VERTICAL |
| ACCESSIBILITY. |
| NOTHING IN THIS CODE RELIEVES THE OWNER OF ANY |
| BUILDING, STRUCTURE, OR FACILITY GOVERNED BY THIS CODE |
| FROM THE DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| LEVELS ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, |
| REGARDLESS OF WHETHER THE ADA STANDARDS FOR ACCESSIBLE |
| DESIGN REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| BUILDING, STRUCTURE OR FACILITY. |
| |
| 2010 FL ACCESSIBILITY CODE 408 LIMITED-USE / |
| LIMITED-APPLICATION ELEVATORS 408.1 GENERAL. |
| LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL COMPLY |
| WITH 408 AND WITH ASME A17.1 (INCORPORATED BY |
| REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1). |
| THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME |
| A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC. |
| |
| 7) NEITHER A2.3, A7.2 NOR E2.1 SHOW ANY SMOKE ALARMS IN |
| THE STAIRWWELL CORRIDOR CEILING OR ON THE ADJACENT |
| CORRIDOR CEILING # 113. THIS WAS A REQUEST FROM BOTH |
| BUILDING & FIRE SINCE THE MEZZANINE DESIGN WAS A HYBRID |
| SYSTEM, WITH A OCCUPANT LOAD GRATER THAN 10, THE 2 HOUR |
| FIRE RATING AROUND THE STAIR CORRIDOR AND EXIT DOOR TO |
| THE EXTERIOR WERE ALSO PART OF THE REQUIREMENTS SINCE |
| THE PLANS LACKED 2 MEANS OF EGRESS THIS DESIGN WAS A |
| EQUIZALENCY TO UNDER ALTERNANTE MATERIALS AND METHODS. |
| |
| 8) HIGH PILE STORAGE RACKING SYSTEM DOES NOT PROVIDE |
| HOW CLOSE THE FIRE SPRINKLERS ARE TO THE RACKING SYSTEM |
| WITH THE BOXED CONTENCE ON THE TOP OF THE RACK. |
| THERE ARE NO MANUFACTURERS INSTALATION INSTRUCTIONS, |
| MAXIMUM LOADING OF RACKS NOR IS THERE INFORMATION AS TO |
| THE ANCHORING OF THE RECK SYSTEMS. |
| 2010 FBC-B 413.1 GENERAL. HIGH-PILED STOCK OR RACK |
| STORAGE IN ANY OCCUPANCY GROUP SHALL COMPLY WITH THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |