2014-04-24 18:07:55 | CONDITIONAL APPROVAL AS FOLLOWS: | | ELECTRICAL PROVISO FOR PERMIT #14040107 | | AS PER NEC 210.8(A)(2) ALL 125 VOLT 15 & 20 AMP OUTLETS | | IN THIS WORKSHOP SHALL BE GFCI PROTECTED. | | AS PER NEC 300.5(B) THE INTERIOR OF A RACEWAY | | UNDERGROUND OR INSIDE A CONCRETE SLAB SHALL BE | | CONSIDERED A WET LOCATION AND THE CONDUCTORS INSIDE | | SHALL BE RATED ACCORDINGLY. | | ALL TRENCHING SHALL REMAIN OPEN FOR INSPECTION. SITE | | TUBES WILL NOT BE ACCEPTED. | | | | RETURNED TO BIN FOR FURTHER REVIEWS |
|