2014-04-09 18:09:27 | BUILDING PLAN REVIEW |
| PERMIT: 14040070 |
| ADD: 400 N FLAGLER # PHA-5 |
| CONT: CONKLING & LEWIS CONSTRUCTION |
| TEL: (561)833-4441 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. APRIL 09/2014 |
| ACTION: DENIED |
| |
| 1) SHEET A101 PLAN NOTES # 5 PROVIDES A PARTIAL WIND |
| DESIGN. |
| MISSING FROM THE DESIGN ARE THE REQUIRED PRESSURES BOTH |
| POSITIVE AND NEGATIVE. FOR WIND DESIGN ABOVE 60 FEET |
| FROM GRADE ASCE 7-10 SHOULD BE USED, 2010 FBC-B |
| 1609.1.1. ARE THE SLIDING GLASS DOORS THAT ARE BEING |
| MOVED TO THE NEW LOCATION IN A END ZONE OR INTERIOR |
| ZONE, THIS WILL ALSO AFFECT THE PRESSURES. |
| |
| |
| |
| 2) PLEASE PROVIDE A RATIONAL ANALYSIS FOR THE FASTENING |
| OF THE FRAMES INTO THE (MWFRS) STRUCTURAL ELEMENTS, |
| COLUMNS, BALCONY FLOOR SLAB AND OVERHEAD BALCONY SLAB. |
| INCLUDE THE TYPE OF ANCHORS, LENGTH, DIAMETER, QUANTITY |
| & SPACING OF ANCHORS. THE REUSING OF THE EXISTING DOORS |
| IS SIMILAR O THE REQUIREMENTS FOR CUSTOM DOORS. |
| 2010 FBC-B 1715.5.3.2 CUSTOM DOORS. CUSTOM (ONE OF A |
| KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN |
| APPROVED TESTING LABORATORY OR BE ENGINEERED IN |
| ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES. |
| |
| 3) THE EXISTING SLIDING GLASS DOORS DID HAVE A OVER |
| HANG, WITH THE NEW PROPOSED LOCATION THEY WILL NEED TO |
| MEET WATER INFILTRATION REQUIREMENTS FOUND IN 2010 |
| FBC-B 1715.5.2.1 TESTING AND LABELING. |
| EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN |
| APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| ONE OF THE FOLLOWING SPECIFICATIONS: |
| |
| ANSI/AAMA/NWWDA 101/I.S. 2 OR ANSI/AAMA/ WDMA/101/I.S. |
| 2/NAFS OR AAMA/WDMA/CSA 101/I.S. 2/A440 OR TAS202 (HVHZ |
| SHALL COMPLY WITH TAS202 UTILIZING ASTM E 1300-98 OR |
| ASTM E 1300-04 OR SECTION 2404). |
| |
| EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE |
| LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING |
| PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT. |
| THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A |
| PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL |
| APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING |
| THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER, |
| POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT |
| MAXIMUM SIZE, GLAZING THICKNESS, IMPACT-RESISTANCE |
| RATING IF APPLICABLE, FLORIDA PRODUCT APPROVAL NUMBER |
| OR MIAMI-DADE PRODUCT APPROVAL NUMBER, APPLICABLE TEST |
| STANDARD(S), AND APPROVED PRODUCT CERTIFICATION AGENCY, |
| TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE |
| PRODUCT APPROVAL. |
| |
| THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE RATING |
| PER REFERENCE STANDARD. THE TEMPORARY SUPPLEMENTAL |
| LABEL SHALL REMAIN ON THE WINDOW OR DOOR UNTIL FINAL |
| APPROVAL BY THE BUILDING OFFICIAL. |
| EXCEPTIONS: |
| 1.DOOR ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE |
| THE DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER |
| INFILTRATION NEED NOT BE TESTED FOR WATER INFILTRATION. |
| 2.DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) |
| RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR |
| WATER INFILTRATION. THE OVERHANG RATIO SHALL BE |
| CALCULATED BY THE FOLLOWING EQUATION: |
| OH RATIO = OH LENGTH/OH HEIGHT |
| WHERE: |
| OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN |
| OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. |
| OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM |
| THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A |
| DOOR. |
| |
| 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |