Plan Review Notes
Plan Review Notes For Permit 14031155
Permit Number 14031155
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-01 11:05:16BURIAL DEPTH PER NEC 300.5 AND 300.5 (D) (3) MAINTAIN A
 MINIMUM CLEARANCE EXTENDING 5' HORIZONTALLY FROM THE
 INSIDE WALL OF THE POOL.
  
 FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN
 REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS
 EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. I
 CAN BE AT 561-805-6717 OR AT [email protected]