Plan Review Notes
Plan Review Notes For Permit 14031098
Permit Number 14031098
Review Stop G
Sequence Number 2
Notes
Date Text
2014-04-11 13:58:22THE NEW SUBMITTAL AS DRAWN WIL NOT WORK THERE IS ONLY
 ONE OUTLET ON A GAS METER, THE PLANS INDICATE A 2 LB
 SYSTEM, HYBRID TO THE MAIN HOUSE TO A 1/2 LB SYSTEM.
 THE PLANS ARE MISSING A SINGLE OUTLET FROM THE METER,
 NIPPLE TEE AND A REGULATOR FROM 2 LB TO 1/2 LB SYSTEM
 INTO THE GARAGE APARTMENT. I'VE SPOKEN WITH DANNY BROWN
 WITH GLEDDIN SPINA, PLANS ARE FORTH COMING WITH
 CORRECTIONS.