2014-04-07 07:24:10 | FUEL GAS PLAN REVIEW |
| PERMIT: 14031098 |
| ADD: 221 GREYMON DR |
| CONT: MONARCH OF PLUMBING |
| TEL: (561)707-4314 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. APRIL 07/2014 |
| ACTION: DENIED |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) 12.GAS |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2010 FUEL GAS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL). |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2010 FUEL GAS CODE SEC. 304 |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| PSI. |
| |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2010 FUEL GAS SEC. 402.2 |
| |
| 10) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING |
| BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR |
| UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN |
| SECTION R315.1.3. |
| R315.1.1 CARBON MONOXIDE ALARM. |
| THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED |
| BY PROVIDING FOR ONE OF THE FOLLOWING ALARM |
| INSTALLATIONS: |
| (1) A HARD-WIRED CARBON MONOXIDE ALARM. |
| (2) A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| ALARM. |
| (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| SMOKE ALARM. |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |