2014-03-28 15:17:35PLUMBING PLAN REVIEW
 PERMIT: 14031087
 ADD: 844 BRADLEY ST
 CONT: DENNIS PORCELAIN ENT
 TEL: (561)248-6839
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 1ST REVIEW
 DATE: FRIDAY MARCH 28/2014
 ACTION: PLUMBING REVIEW: PROVISO
 1) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FOR THE
 RENOVATION OF THE BATHROOM, REMOVAL OF FIXTURES, STOPS
 AND OR VALVES AND NEW SHOWER ENCLOSURE.
 2) P2503.6 SHOWER LINER TEST.
 WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER TIGHT
 BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION
 P2709.2, THE COMPLETED LINER INSTALLATION SHALL BE
 TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED
 WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA
 SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT
 LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD.
 WHERE A THRESHOLD OF AT LEAST 2 INCHES HIGH DOES NOT
 EXIST, A TEMPORARY THRESHOLD SHALL BE CONSTRUCTED TO
 RETAIN THE TEST WATER IN THE LINED FLOOR OR RECEPTOR
 AREA TO A LEVEL NOT LESS THAN 2 INCHES DEEP MEASURED AT
 THE THRESHOLD. THE WATER SHALL BE RETAINED FOR A TEST
 PERIOD OF NOT LESS THAN 15 MINUTES AND THERE SHALL BE
 NO EVIDENCE OF LEAKAGE.
 3) P2709.2 LINING REQUIRED.
 THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING ON-SITE
 BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH ONE OF
 THE FOLLOWING MATERIALS:
 1. SHEET LEAD,
 2. SHEET COPPER,
 3. PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D
 4068 OR ASTM D 4551,
 4. HOT MOPPING IN ACCORDANCE WITH SECTION P2709.2.3 OR
 5. SHEET-APPLIED LOAD-BEARING, BONDED WATERPROOF
 MEMBRANES THAT COMPLY WITH ANSI A118.10.
 THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 3 INCHES
 (76 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS
 THAN 3 INCHES (76 MM) ABOVE FINISHED THRESHOLDS.
 SHEET-APPLIED LOAD BEARING, BONDED WATERPROOF MEMBRANES
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
 EXCEPTIONS:
 1. FLOOR SURFACES UNDER SHOWERHEADS PROVIDED FOR
 RINSING LAID DIRECTLY ON THE GROUND.
 2. SHOWER COMPARTMENTS WHERE THE FINISHED SHOWER DRAIN
 IS DEPRESSED A MINIMUM OF 2 INCHES (51 MM) BELOW THE
 SURROUNDING FINISHED FLOOR ON THE FIRST FLOOR LEVEL AND
 THE SHOWER RECESS IS POURED INTEGRALLY WITH THE
 ADJOINING FLOOR.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  