2014-03-28 15:17:35 | PLUMBING PLAN REVIEW |
| PERMIT: 14031087 |
| ADD: 844 BRADLEY ST |
| CONT: DENNIS PORCELAIN ENT |
| TEL: (561)248-6839 |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| 1ST REVIEW |
| DATE: FRIDAY MARCH 28/2014 |
| ACTION: PLUMBING REVIEW: PROVISO |
| 1) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FOR THE |
| RENOVATION OF THE BATHROOM, REMOVAL OF FIXTURES, STOPS |
| AND OR VALVES AND NEW SHOWER ENCLOSURE. |
| 2) P2503.6 SHOWER LINER TEST. |
| WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER TIGHT |
| BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION |
| P2709.2, THE COMPLETED LINER INSTALLATION SHALL BE |
| TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED |
| WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA |
| SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT |
| LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD. |
| WHERE A THRESHOLD OF AT LEAST 2 INCHES HIGH DOES NOT |
| EXIST, A TEMPORARY THRESHOLD SHALL BE CONSTRUCTED TO |
| RETAIN THE TEST WATER IN THE LINED FLOOR OR RECEPTOR |
| AREA TO A LEVEL NOT LESS THAN 2 INCHES DEEP MEASURED AT |
| THE THRESHOLD. THE WATER SHALL BE RETAINED FOR A TEST |
| PERIOD OF NOT LESS THAN 15 MINUTES AND THERE SHALL BE |
| NO EVIDENCE OF LEAKAGE. |
| 3) P2709.2 LINING REQUIRED. |
| THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING ON-SITE |
| BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH ONE OF |
| THE FOLLOWING MATERIALS: |
| 1. SHEET LEAD, |
| 2. SHEET COPPER, |
| 3. PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D |
| 4068 OR ASTM D 4551, |
| 4. HOT MOPPING IN ACCORDANCE WITH SECTION P2709.2.3 OR |
| 5. SHEET-APPLIED LOAD-BEARING, BONDED WATERPROOF |
| MEMBRANES THAT COMPLY WITH ANSI A118.10. |
| THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 3 INCHES |
| (76 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS |
| THAN 3 INCHES (76 MM) ABOVE FINISHED THRESHOLDS. |
| SHEET-APPLIED LOAD BEARING, BONDED WATERPROOF MEMBRANES |
| SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS. |
| EXCEPTIONS: |
| 1. FLOOR SURFACES UNDER SHOWERHEADS PROVIDED FOR |
| RINSING LAID DIRECTLY ON THE GROUND. |
| 2. SHOWER COMPARTMENTS WHERE THE FINISHED SHOWER DRAIN |
| IS DEPRESSED A MINIMUM OF 2 INCHES (51 MM) BELOW THE |
| SURROUNDING FINISHED FLOOR ON THE FIRST FLOOR LEVEL AND |
| THE SHOWER RECESS IS POURED INTEGRALLY WITH THE |
| ADJOINING FLOOR. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO/ SENIOR COMMERCIAL COMBINATION |
| PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |