Plan Review Notes
Plan Review Notes For Permit 14031086
Permit Number 14031086
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-02 12:03:04THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO
 BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR
 AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE
 SYSTEM.
  
 2. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 3. THE LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.