Plan Review Notes For Permit 14031086 |
Permit Number |
14031086 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-02 12:03:04 | THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE | | FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU | | OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE. | | | | 1. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO | | BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR | | AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE | | SYSTEM. | | | | 2. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A | | CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA | | 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE | | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION | | BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | 3. THE LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE | | ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION | | PERIOD. | | | | 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. |
|