Plan Review Notes
Plan Review Notes For Permit 14031064
Permit Number 14031064
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-01 13:48:25505.2.3 DAYLIGHT ZONE CONTROL.
 DAYLIGHT ZONES, AS DEFINED BY THIS CODE, SHALL BE
 PROVIDED WITH INDIVIDUAL CONTROLS THAT CONTROL THE
 LIGHTS INDEPENDENT OF GENERAL AREA LIGHTING. CONTIGUOUS
 DAYLIGHT ZONES ADJACENT TO VERTICAL FENESTRATION ARE
 ALLOWED TO BE CONTROLLED BY A SINGLE CONTROLLING DEVICE
 PROVIDED THAT THEY DO NOT INCLUDE ZONES FACING MORE
 THAN TWO ADJACENT CARDINAL ORIENTATIONS (I.E., NORTH,
 EAST, SOUTH, WEST). DAYLIGHT ZONES UNDER SKYLIGHTS MORE
 THAN 15 FEET (4572 MM) FROM THE PERIMETER SHALL BE
 CONTROLLED SEPARATELY FROM DAYLIGHT ZONES ADJACENT TO
 VERTICAL FENESTRATION.
  
 EXCEPTION: DAYLIGHT SPACES ENCLOSED BY WALLS OR CEILING
 HEIGHT PARTITIONS AND CONTAINING TWO OR FEWER LIGHT
 FIXTURES ARE NOT REQUIRED TO HAVE A SEPARATE SWITCH FOR
 GENERAL AREA LIGHTING.
  
 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 EXCEPTION: LIGHTING FOR COVERED VEHICLE ENTRANCES OR
 EXITS FROM BUILDINGS OR PARKING STRUCTURES WHERE
 REQUIRED FOR SAFETY, SECURITY, OR EYE ADAPTATION.