2014-04-23 15:28:49455 HIBISCUS STREET
 PERMIT #14030990
 MASTER #13070994
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER LOCAL AHJ AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION IN LIEU OF A
 SUPERVISORY SIGNAL.
  
 SHEET FA-01: PROVIDE VISUAL ALARM NOTIFICATION IN
 WOMENS' AND MENS' BATHROOMS (#122 & #123).
  
 SHEET FA-02: ADDITIONAL FIRE ALARM NOTIFICATION
 APPLIANCE(S) ARE NEEDED BETWEEN COLUMN LINES 7 - 10 IN
 CORRIDOR #1 (201). TYPICAL ALL FLOORS
  