2014-03-25 18:39:36RE-ROOF REVISION, BUILDING REVIEW COMMENTS.
  
  
 1- NOA 13-0129.19 SUBMITTED IS FOR MODIFIED BITUMEN
 ROOFING SYSTEMS OVER STEEL DECKS. IT DOESN'T APPLY TO
 THE EXISTING CONDITIONS. NEED TO PROVIDE NOA THAT
 MATCHES EXISTING CONDITIONS AND PROPOSED INSTALLATION.
 NEED PRODUCT APPROVAL (2 COPIES) FOR ROOFING SYSTEMS
 OVER LIGHTWEIGHT CONCRETE DECK. AND, NEED TO SELECT
 ASSEMBLY THAT SHOWS FASTENING TO THE STEEL DECK THROUGH
 THE LIGHT WEIGHT CONCRETE AS REQUIRED BY DCA RULE 9N-3.
  
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS USING THE
 PRODUCT APPROVAL ASSEMBLY REQUIRED BY ITEM #1 ABOVE.
 SEC. 1609 OF FBC-2010
  