Plan Review Notes
Plan Review Notes For Permit 14030926
Permit Number 14030926
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-25 09:24:10THERE IS AN EXISTING SERVICE WITH MULTIPLE METERS
 CURRENTLY SERVING THIS BUILDING. THE NEC ARTICLE 230.2
 STATES THAT A BUILDING MAY BE SERVED BY ONLY ONE
 SERVICE. PLEASE SHOW THE LOCATION OF THE EXISTING
 SERVICE AND INCLUDE THE LOCATION OF THE PROPOSED
 SERVICE. ADDITIONALLY WE WILL NEED THE FOLLOWING: A
 FLOOR PLAN INDICATING THE TENANT SPACES FOR THE WHOLE
 BLDG. ZONING WILL NEED TO APPROVE THE ADDITIONAL
 TENANT. BUILDING PLANS ARE REQUIRED TO SHOW THE TENANT
 SEPARATION. RECALCULATE THE LOAD TO JUSTIFY THE 400AMP
 SERVICE.