2014-03-26 16:41:57 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW | | COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE | | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. | | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. | | | | 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | 3. PROVIDE DIMENSIONS ON THE SITE PLAN FBC 107, | | INCLUDING THE DIMENSIONS OF THE AWNING AS WELL AS | | DISTANCE TO PROPERTY LINE. | | | | 4. THE AWNING ENGINEERING CONFLICTS WITH THE SITE PLAN. | | SITE PLAN SHOWS A NARROW LONG AWNING ATTCHED TO THE | | BUILDING, ENGINEERING IS FOR A NEARLY SQUARE (11'6" X | | 8'5") AWNING. |
|