Plan Review Notes
Plan Review Notes For Permit 14030881
Permit Number 14030881
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-16 17:04:552010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND LOAD CALCULATIONS FOR THE LIGHTING POLES
 FROM PROFESSIONAL ENGINEER CHRISTOPHER PLY THAT ARE
 STAPLED TO THE LIGHTING PLANS DO NOT HAVE THE SITE
 ADDRESS TO TIE IT TO THIS PROJECT. FAC 61G15-23.002
  
 2) THE LIGHTING POLE CALCULATIONS ARE FOR A SIDE ARM
 MOUNT AND THE ONE SHOWN ON THE PLAN HAS THE LAMP
 MOUNTED DIRECTLY ON THE TOP OF THE POLE. PLEASE
 CLARIFY. CITY AMENDMENTS 107.2.1
  
 3) IT APPEARS THAT THE LIGHTING POLE CALCULATIONS WERE
 DONE BY A DELEGATED ENGINEER. IF THIS IS THE CASE, THEN
 THE ENGINEER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THEM IN WRITING. FAC 61G15-30.005
  