Plan Review Notes
Plan Review Notes For Permit 14030879
Permit Number 14030879
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-27 08:18:22MECHANICAL PROVISO:
 1) SHEET M2.1 NOTE 2 INDICATES A ALTERNATE LOCATION FOR
 THE VAV INTO THE TENANT SPACE.
 A REVISION IS REQUIRED WITH NEW LOCATION, IF THE VAV
 BOX IS NOT MOVED INTO THE TENANT SPACE
 A FIRE DAMPER WILL BE REQUIRED PER SECTION 2010 FBC-M
 607.5.3.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]