2014-04-15 17:51:32IN ADDITION TO THE FIRE DEPARTMENT COMMENTS WHICH CALL
 FOR THE ADDITION OF A COUPLE OF MANUAL PULL STATIONS
 ETC. PROVIDE A DRAWING OF THE PROPOSED SMOKE BARRIER
 DOOR SHOWING CORRIDOR HEIGHTS IN RELATION TO DOOR
 HEIGHTS. INDICATE IF DOOR RELEASE IS DIRECTLY FROM THE
 RESPECTIVE SMOKE DETECTOR OR FROM THE FACP. REARRANGE
 THE DOORS AND HOLDERS SO THAT THE DOORS SWING IN THE
 NORMAL PATH OF EGRESS. PLEASE INDICATE ON THE DRAWING
 IF THE BLDG. IS FULLY SPRINKLED.