2014-04-15 17:51:32 | IN ADDITION TO THE FIRE DEPARTMENT COMMENTS WHICH CALL | | FOR THE ADDITION OF A COUPLE OF MANUAL PULL STATIONS | | ETC. PROVIDE A DRAWING OF THE PROPOSED SMOKE BARRIER | | DOOR SHOWING CORRIDOR HEIGHTS IN RELATION TO DOOR | | HEIGHTS. INDICATE IF DOOR RELEASE IS DIRECTLY FROM THE | | RESPECTIVE SMOKE DETECTOR OR FROM THE FACP. REARRANGE | | THE DOORS AND HOLDERS SO THAT THE DOORS SWING IN THE | | NORMAL PATH OF EGRESS. PLEASE INDICATE ON THE DRAWING | | IF THE BLDG. IS FULLY SPRINKLED. |
|