Plan Review Notes For Permit 14030857 |
Permit Number |
14030857 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-26 16:50:45 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE THE FOLLOWING INFORMATION: | | | | OCCUPANCY CLASSIFICATION FBC CHAPTER 3. IF YOU ARE | | UNABLE TO PROVIDE A CLASSIFICATION, PROVIDE A | | DESCRIPTION OF USE OF THE SPACE(S) AND A CLASSIFICATION | | WILL BE DETERMINED. | | | | ARE FIRE EXIT HARDWARE PROPOSED? (PANIC DEVICES) FBC | | 1008.1.10: ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 | | AMPERES OR MORE AND OVER 6' WIDE THAT CONTAIN | | OVERCURRET DEVICES, SWITCHING DEVICES OR CONTROL | | DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE | | EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. IF | | YOU ARE USING AN EXCEPTION FROM THE EXISTING BUILDING | | CODE, PLEASE CITE CODE SECTION AND METHOD OF COMPLIANCE | | FBC 2010 EXISTING BUILDING 101. | | | | WHAT IS THE FIRE RATING FOR THE WALL? | | | | WHAT IS THE PROPOSED FIRE RATING FOR THE PROPOSED | | DOORS? | | | | |
|