Plan Review Notes
Plan Review Notes For Permit 14030857
Permit Number 14030857
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-26 16:50:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE THE FOLLOWING INFORMATION:
  
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3. IF YOU ARE
 UNABLE TO PROVIDE A CLASSIFICATION, PROVIDE A
 DESCRIPTION OF USE OF THE SPACE(S) AND A CLASSIFICATION
 WILL BE DETERMINED.
  
 ARE FIRE EXIT HARDWARE PROPOSED? (PANIC DEVICES) FBC
 1008.1.10: ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200
 AMPERES OR MORE AND OVER 6' WIDE THAT CONTAIN
 OVERCURRET DEVICES, SWITCHING DEVICES OR CONTROL
 DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE
 EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. IF
 YOU ARE USING AN EXCEPTION FROM THE EXISTING BUILDING
 CODE, PLEASE CITE CODE SECTION AND METHOD OF COMPLIANCE
 FBC 2010 EXISTING BUILDING 101.
  
 WHAT IS THE FIRE RATING FOR THE WALL?
  
 WHAT IS THE PROPOSED FIRE RATING FOR THE PROPOSED
 DOORS?
  
  