2014-04-16 12:32:03 | IT APPEARS AND ADDITIONAL STROBE DEVICE NEAR CHAIR 18 | | AND CHAIR 19 IS NEEDED TO PROVIDE ADEQUATE VISUAL | | NOTIFICATION. | | | | PER LOCAL REQUIREMENTS, DUCT DETECTORS SHALL ACTIVATE A | | GENERAL ALARM CONDITION IN LIEU OF A SUPERVISORY | | CONDITION. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WPB FIRE RESCUE | | 561.804.4752 | | [email protected] |
|