Plan Review Notes
Plan Review Notes For Permit 14030855
Permit Number 14030855
Review Stop P
Sequence Number 1
Notes
Date Text
2014-04-01 06:19:08NO PLUMBING SHEETS WERE SUBMITTED FOR THE FOUNDATION
 PERMIT.
 PLUMBING PROVISO:
 2010 FBC-P 305.5 PIPES THROUGH OR UNDER FOOTINGS OR
 FOUNDATION WALLS. ANY PIPE THAT PASSES UNDER A FOOTING
 OR THROUGH A FOUNDATION WALL SHALL BE PROVIDED WITH A
 RELIEVING ARCH, OR A PIPE SLEEVE PIPE SHALL BE BUILT
 INTO THE FOUNDATION WALL. THE SLEEVE SHALL BE TWO PIPE
 SIZES GREATER THAN THE PIPE PASSING THROUGH THE WALL.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676