Plan Review Notes For Permit 14030855 |
Permit Number |
14030855 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-01 06:19:08 | NO PLUMBING SHEETS WERE SUBMITTED FOR THE FOUNDATION | | PERMIT. | | PLUMBING PROVISO: | | 2010 FBC-P 305.5 PIPES THROUGH OR UNDER FOOTINGS OR | | FOUNDATION WALLS. ANY PIPE THAT PASSES UNDER A FOOTING | | OR THROUGH A FOUNDATION WALL SHALL BE PROVIDED WITH A | | RELIEVING ARCH, OR A PIPE SLEEVE PIPE SHALL BE BUILT | | INTO THE FOUNDATION WALL. THE SLEEVE SHALL BE TWO PIPE | | SIZES GREATER THAN THE PIPE PASSING THROUGH THE WALL. | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|