2014-11-27 09:28:37 | 1)TABLE 403.1 FOOTNOTE "G" OF 2010 FL. PLUMBING CODE |
| REQUIRES A UNISEX BATHROOM IN ASSEMBLY OCCUPANCIES |
| WHERE AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER |
| CLOSETS ARE REQUIRED IN ACCORDANCE WITH THE 2010 FPC |
| SEC.403.5. SHOW THE REQUIRED UNISEX TOILET ROOM ON THE |
| PLANS AND PROVIDE A SANITARY AND WATER RISER FOR |
| REVIEW. 2ND REQUEST. THE UNISEX TOILET ROOM SHALL |
| COMPLY WITH THE FL. ACCESSIBILITY CODE. |
| 2) SUBMIT AN ENLARGED RESTROOM FLOOR PLAN FOR THE FIRST |
| FLOOR. SHOW ALL REQUIRED FLOOR SPACE FOR THE |
| HANDICAPPED FIXTURES. THE RESTROOMS SHALL FULLY COMPLY |
| WITH THE 2010 FL. ACCESSIBILITY CODE.THE TOILET |
| COMPARTMENTS SHALL COMPLY WITH FAC SEC.604.8.1.6.SINCE |
| THIS IS A CHANGE OF OCCUPANCY. 2ND REQUEST. |
| 3) SHT. P-2 - THE FIRST FLOOR SANITARY PLAN IS DRAWN |
| VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A PLAN THAT |
| IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2001 FBC |
| SEC. 107.2.1. 2ND REQUEST. |
| 4) THE RESTROOMS ON THE 2ND FLOOR SHALL FULLY COMPLY |
| WITH THE FL. ACCESSIBILITY CODE. THE TOILET |
| COMPARTMENTS SHALL COMPLY WIT FAC SEC.604.8.1.6.SHOW |
| ALL THE REQUIRED CLEAR FLOOR SPACE PER FAC SEC. 306 & |
| 604.3.2ND REQUEST. |
| 5) SHT. P-4 - THE 2ND FLOOR SANITARY ISOMETRIC FOR THE |
| WOMEN'S RESTROOM #205 HAS A DRY VENT FOR THE P-1 |
| FIXTURE. EVERY DRY VENT CONNECTING TO A HORIZONTAL |
| DRAIN SHALL COMPLY WITH THE 2010 FPC SEC.905.3. 2ND |
| REQUEST. |
| 6) THE FLOOR DRAINS ON THE FIRST FLOOR SANITARY |
| ISOMETRIC ARE NOT VENTED. PROVIDE THE PROPER SIZE VENTS |
| PER THE FPC SEC.906.1, 901.2. 2ND REQUEST. |
| 7) THE P-5 FIXTURE SHALL BE PROPERLY TRAPPED. FPC |
| 1002.1. 2ND REQUEST. |
| 8) THE SINGLE FLOOR DRAIN IN THE BAR AREA (#209) IS NOT |
| VENTED.FPC SEC.906.1.2ND REQUEST. |
| 9)THE NUMBER OF WATER CLOSETS BEING WET VENTED IN THE |
| FIRST AND SECOND FLOOR RESTROOMS EXCEEDS THE NUMBER |
| PERMITTED BY FPC SEC. 909. ALSO, URINALS ARE NOT |
| PERMITTED ON THE HORIZONTAL WET VENTS. 2ND REQUEST. |
| 10) SHT. P-3 - THE 2ND FLOOR DOMESTIC (WATER PLAN) IS |
| DRAWN VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A |
| PLAN THAT IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO |
| 2001 FBC SEC. 107.2.1. |
| 11) THE RESPONSE NARRATIVE FROM ELLIS & GRITTER |
| ADDRESSES COMMENTS FROM THE APRIL REVIEW NOT THE |
| NOVEMBER REVIEW. |
| |