Plan Review Notes
Plan Review Notes For Permit 14030818
Permit Number 14030818
Review Stop B
Sequence Number 3
Notes
Date Text
2014-12-08 12:14:00BUILDING PLAN REVIEW
 PERMIT: 14030818
 ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF
 OCCUPANY/INTERIOR & EXTERIOR
 CONT: JM PROPERTIES OF WEST PALM BEACH, INC
 TEL: (561)756-5744
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BLDG TYPE III-B SPRINKLERED
  
 3RD REVIEW
 DATE: MON. DEC. 08/ 2014
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT
 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2
 APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE.
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
  
 CONTRACTOR IS PROCEEDING AT THEIR OWN RISK!!! 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 105.13 PHASED PERMIT
 APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS
 AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF
 FOUNDATIONS OR ANY OTHER PART OF A BUILDING OR
 STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS FOR THE
 WHOLE BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 1) REVISION REQUIRED. AN ARCHITECTURAL SHEET IS
 REQUIRED SHOWING THE SCHEMATIC LAYOUT FOR THE FIRE
 SPRINKLERS, A FULL NFPA 13 SYSTEM WILL BE REQUIRED.
 A HOLD WILL BE PUT ON THE CERTIFICATE OF OCCUPANCY
 UNTIL THIS REVISION IS SUBMITTED AND APPROVED. SEPARATE
 FIRE SPRINKLER PLANS WILL ALSO NEED TO BE SUBMITTED BY
 THE ENGINEER OF RECORD AND REVIEWED BY THE DESIGNER OF
 RECORD WITH THIER SHOP DRAWING STAMP OF APPROVAL,
 APPROVED OR APPROVED WITH COMMENTS.
  
 107.2.1.1 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP
 DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S) SHALL BE
 SUBMITTED TO INDICATE CONFORMANCE WITH THIS CODE AND
 THE CONSTRUCTION DOCUMENTS AND SHALL BE APPROVED PRIOR
 TO THE START OF SYSTEM INSTALLATION. SHOP DRAWINGS
 SHALL CONTAIN ALL INFORMATION AS REQUIRED BY THE
 REFERENCED INSTALLATION STANDARDS IN CHAPTER 9.
  
 3RD REQUEST. MON. DEC. 08/2014 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE
 SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE
 SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE
 ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR
 NON-SPRINKLERED BUILDING.
 2010 EXST BLDG CODE 904.1 GENERAL.
 FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B F] 903.2.1.2 GROUP A-2.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2);
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE;
  
 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 BUILDING PROVISO:
 10C) FRONT ENTRY REDESIGN:
 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:(31)(A) EXTERIOR DOORS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  