2014-10-14 15:04:38 | 1) NEITHER THE COVERSHEET NOR ANY OF THE PLUMBING |
| SHEETS PROVIDE THE REQUIRED MINIMUM FIXTURE COUNT PER |
| THE 2010 FBC-PLUMBING, TABLE 403.1. |
| 2) FOOTNOTE "G" OF TABLE 403.1 OF THE 2010 |
| FBC-PLUMBING, REQUIRES A UNISEX BATHROOM IN MERCANTILE |
| AND ASSEMBLY OCCUPANCIES WHERE AN AGGREGATE OF SIX OR |
| MORE MALE AND FEMALE WATER CLOSETS ARE REQUIRED. |
| 3) SUBMIT AN ENLARGED RESTROOM FLOOR PLAN FOR THE THE |
| FIRST FLOOR. |
| 4) THE RESTROOMS ON THE SECOND FLOOR SHALL COMPLY WITH |
| THE FLORIDA ACCESSIBILITY CODE FOR BUILING |
| CONSTRUCTION. |
| 5) SHT. P-2 - THE 1ST FLOOR SANITARY PLAN IS ILLEGIBLE. |
| SUBMIT A PLAN THAT IS CLEAR IN DETAIL. WPB AMEND. TO |
| 2010 FBC SEC. 107.2.1. |
| 6) THE 2ND FLOOR SANITARY ISOMETRIC HAS DRY VENTS FOR |
| THE P-1 FIXTURES. EVERY DRY VENT CONNECTING TO A |
| HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| THE HORIZONTAL DRAIN PIPE PER THE 2010 FPC SEC.905.3. |
| 7) THE FLOOR DRAINS ON THE FIRST FLOOR ARE NOT VENTED. |
| FPC SEC.906.1. 901.2. |
| 8) THE SANITARY LINE FOR FIXTURE P-1 ON THE FIRST FLOOR |
| CONNECTS TO NOTHING. CLARIFY. |
| 9) P-5 FIXTURES REQUIRE TRAPS. |
| 10) THE SINGLE FLOOR DRAIN IN THE BAR AREA ON THE |
| SECOND FLOOR IS NOT VENTED. FPC SEC.906.1 |
| 11) THE NUMBER OF WATER CLOSETS BEING WET VENTED IN THE |
| SECOND FLOOR RESTROOMS EXCEEDS THE NUMBER PERMITTED BY |
| SEC.909 OF THE FPC. ALSO, URINALS ARE NOT PERMITTED ON |
| A WET VENT. |
| 12) BASED ON THE SHOWN OCCUPANT LOAD, THE MINIMUM |
| NUMBER OF REQUIRED PLUMBING FIXTURES ARE AS FOLLOWS: |
| A) 7 WATER CLOSETS, 4 LAVS FOR THE MALES |
| B) 7 WATER CLOSETS, 4 LAVS FOR THE FEMALES |
| C) 1 SERVICE SINK |
| D) 2 DRINKING FOUNTAINS |
| 13) CITY RECORDS ( PERMIT #03060274 ) SHOW THE SECOND |
| FLOOR OF THIS BUILDING AS APARTMENTS, WHICH IS AN R-2 |
| OCCUPANCY. THIS WILL BE CONSIDERED A CHANGE OF |
| OCCUPANCY AND MUST COMPLY WITH CHAPT.9 , SECS. 902-913 |
| OF THE 2010 FBC, EXISTING BUILDING CODE. |
| |