2014-10-08 08:15:40 | BUILDING PLAN REVIEW |
| PERMIT: 14030818 |
| ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF |
| OCCUPANY/INTERIOR & EXTERIOR |
| CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| TEL: (561)756-5744 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| BLDG TYPE III-B SPRINKLERED |
| |
| 2ND REVIEW |
| DATE: WEDNESDAY 08/ 2014 |
| ACTION: DENIED |
| |
| THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| GROUP. |
| |
| 1) THE COVERSHEET A0.0 INDICATES THE OCCUPANCY AS A A2 |
| NIGHTCLUB SINCE THERE IS NO KITCHEN SHOWN ON THE PLANS. |
| SHEET A1.2 LIST OCCUPANT LOADS FOR EACH FLOOR EXAMPLE |
| THE 2ND FLOOR LIST CUSTOMER AREA 992 SQ. FT./ 198 |
| OCCUPANTS + 32 +16+ 8 +6 +10. PLEASE PROVIDE WHERE THE |
| ADDITIONAL |
| OCCUPANT LOADS ARE TAKEN FROM, INDICATE THE AREA AND |
| LOADING FACTOR. |
| 2010 FBC-B 1004.2 INCREASED OCCUPANT LOAD. |
| THE OCCUPANT LOAD PERMITTED IN ANY BUILDING, OR PORTION |
| THEREOF, IS PERMITTED TO BE INCREASED FROM THAT NUMBER |
| ESTABLISHED FOR THE OCCUPANCIES IN TABLE 1004.1.1, |
| PROVIDED THAT ALL OTHER REQUIREMENTS OF THE CODE ARE |
| ALSO MET BASED ON SUCH MODIFIED NUMBER AND THE OCCUPANT |
| LOAD DOES NOT EXCEED ONE OCCUPANT PER 7 SQUARE FEET |
| (0.65 M2) OF OCCUPIABLE FLOOR SPACE. WHERE REQUIRED BY |
| THE BUILDING OFFICIAL, AN APPROVED AISLE, SEATING OR |
| FIXED EQUIPMENT DIAGRAM SUBSTANTIATING ANY INCREASE IN |
| OCCUPANT LOAD SHALL BE SUBMITTED. WHERE REQUIRED BY THE |
| BUILDING OFFICIAL, SUCH DIAGRAM SHALL BE POSTED. |
| |
| 2) 2ND REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| |
| THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE |
| SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE |
| SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE |
| ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR |
| NON-SPRINKLERED BUILDING. |
| 2010 EXST BLDG CODE 904.1 GENERAL. |
| FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| OF OCCUPANCY CLASSIFICATION. |
| 912.2 FIRE PROTECTION SYSTEMS. |
| FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTIONS 912.2.1 AND 912.2.2. |
| |
| EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. |
| |
| 2010 FBC-B F] 903.2.1.2 GROUP A-2. |
| AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING |
| CONDITIONS EXISTS: |
| 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2); |
| 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE; |
| |
| EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| |
| 3) COMPLIED, NEW INSWING FOLDING DOOR SYSTEM SHOWN ON |
| PLANS. |
| |
| |
| 4) SEMI-COMPLIED. THE (2) EXISTING SWING DOORS NEED TO |
| SHOW THEY DO NOT SWING OUT OVER THE PROPERTY LINE AND |
| IN COMPLIANCE WITH 2010 FBC-B |
| 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN |
| HEIGHT. PROVIDE A SITE PLAN AND OR SURVEY SHOWING CODE |
| COMPLIANCE. |
| |
| 5) 2ND REQUEST. THE PLANS DO NOT HAVE ANY DETAILS AS |
| FAR AS THE SILL FOR THE FOLDING DOOR SYSTEM, PLEASE |
| PROVIDE COMPLIANCE WITH 2010 FL ACCESS CODE 404.2.5 |
| THRESHOLDS. |
| THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 6) SEMI-COMPLIED. SHEET A1.1 THE FRONT STAIR IS AN |
| UNENCLOSED EXIT STAIRWAY AND TAKING THE EXEMPTION# 3 IN |
| SECTION 1016.1. PLEASE PROVIDE THE WIDTH BOTH STAIRS |
| AND THE ALLOWABLE OCCUPANT LOADS EACH STAIR WILL |
| ACCEPT. 2010 FBC-B 1005.1. |
| |
| 7) SHEET A1.1 THE ELEVATOR MACHINE ROOM 2010 FBC-B |
| 3006.4. PLEASE NOTE THE CEILING OF THIS ROOM WILL NEED |
| TO BE FIRE RATED AS WELL IT WILL ABUT THE FRAMING |
| MEMBERS OF THE STAIRWELL. 2010 FBC-B 1022.1 & 707 |
| HORIZONTAL ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER |
| TABLE 715.4. |
| |
| 8-9) COMPLIED. |
| |
| 10) STRUCTURAL SHEET S-1: |
| |
| 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE |
| FOLLOWING : |
| 10A)(1) TB- HEIGTH NOT PROVIDED. NOTE TO MATCH |
| EXISTING, NOTE THIS IS A (2) STORY SHAFT AND THERE IS |
| NO DETAIL AS TO HOW THE TOP OF THE SHAFT FINISHES, |
| BELOW THE ROOF OR ABOVE THE ROOF. 2010 FBC-B 708.12 |
| 10A)(2) COMPLIED. |
| 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE |
| FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR. |
| 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE |
| SECOND FLOOR. |
| 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT |
| THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE |
| UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION |
| OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR |
| PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE |
| FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT |
| ENCLOSURE. |
| |
| |
| 10B)COMPLIED. |
| |
| 10C) FRONT ENTRY REDESIGN: |
| 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS:(31)(A) EXTERIOR DOORS. |
| |
| 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL |
| NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS |
| WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE |
| SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA. |
| THE BUILDING OFFICIAL MAY REQUIRE DETAILS, |
| COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY |
| TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE |
| BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO |
| BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE |
| AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS |
| STATE LAW REQUIRES. |
| SHEET S-1 INDICATES A DETAIL FOR THE FRONT ENTRY SHEET |
| S-2 DETAIL # 7. THIS DETAIL INDICATES THE INSTALATION |
| OF A W 16X31 BEAM TO AC1540 C CHANNEL. |
| IN THIS SAME DETAIL AT THE BOTTOM OF THE DETAIL HERE |
| APPEARS TO BE A BOX BEAM, THERE IS NO INFORMATION ON |
| THE SIZE OF THIS BEAM OR HOW IT IS TO INSTALLED, IT |
| APPEARS THIS THIS THE STRUCTURAL MEMBER (HEADER) FOR |
| THE FOLDING DOOR SYSTEM. |
| |
| 10D) NEW COMMENT: THE NEW FRONT ENTRY CONFIGURATION NOW |
| CONSIST OF A SINGLE SWING DOOR AND A FOLDING DOOR |
| SYSTEM THAT HAS INCORPARATED A SWING DOOR AS PART OF |
| THE FOLDING DOOR SYSTEM. PLEASE NOTE THAT BOTH OF THE |
| FRONT SWING DOORS WILL BE REQUIRED AS PART OF THE |
| EGRESS DOORS SINCE A 3'-0" DOOR WILL ALLOW 170 |
| OCCUPANTS. PLEASE PROVIDE COMPLIANCE WITH 1008.1.10 |
| PANIC AND FIRE EXIT HARDWARE, HOW WILL THIS REQUIREMENT |
| WORK AS PART OF THE FOLDING DOOR SYSTEM? |
| |
| 11) COMPLIED. |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |