2014-04-24 13:12:43MECHANICAL PLAN DENIED
 1) PROVIDE ENERGY CALCULATION WITH THE
 PLAN PER SECTION 503.2.1 CALCULATION
 OF HEATING AND COOLING LOADS. 2010
 FLORIDA ENERGY CODE.
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CURB TO ROOF TIEDOWN AND CONDENSER
 TO CURB TIEDOWN .
 PROVIDE TYPE OF FASTENERS SIZE AND HOW FAR APART
 PER SECTION 303.12 WIND RESISTANCE 2010 FBC (M)