Plan Review Notes For Permit 14030818 |
Permit Number |
14030818 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-24 13:12:43 | MECHANICAL PLAN DENIED | | 1) PROVIDE ENERGY CALCULATION WITH THE | | PLAN PER SECTION 503.2.1 CALCULATION | | OF HEATING AND COOLING LOADS. 2010 | | FLORIDA ENERGY CODE. | | 2) PROVIDE A DETAIL FROM THE ENGINEER | | ON THE CURB TO ROOF TIEDOWN AND CONDENSER | | TO CURB TIEDOWN . | | PROVIDE TYPE OF FASTENERS SIZE AND HOW FAR APART | | PER SECTION 303.12 WIND RESISTANCE 2010 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|