Plan Review Notes
Plan Review Notes For Permit 14030818
Permit Number 14030818
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-02 13:44:06THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. A FIRE SPRINKLER AND FIRE ALARM SYSTEM IS REQUIRED
 FOR THIS PROJECT.
  
 2. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO
 BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR
 AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE
 SYSTEM.
  
 3. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 4. CURRENT LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
  
 5. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 6. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 7. TWO (2) ADDITIONAL EXIT SIGNS ARE REQUIRED AS
 INDICATED DUE TO THE PROPOSED EXIT SIGNS BEING NOT
 VISIBLE FROM THE OCCUPIED AREAS THEY SERVE.
  
 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
  