2014-04-02 13:44:06 | THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE |
| FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU |
| OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE. |
| |
| 1. A FIRE SPRINKLER AND FIRE ALARM SYSTEM IS REQUIRED |
| FOR THIS PROJECT. |
| |
| 2. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO |
| BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR |
| AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, |
| ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE |
| SYSTEM. |
| |
| 3. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A |
| CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA |
| 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE |
| SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| BUREAU PRIOR TO ANY WORK ON THE SYSTEM. |
| |
| 4. CURRENT LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE |
| ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION |
| PERIOD. |
| |
| 5. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| 6. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| DOOR. |
| |
| 7. TWO (2) ADDITIONAL EXIT SIGNS ARE REQUIRED AS |
| INDICATED DUE TO THE PROPOSED EXIT SIGNS BEING NOT |
| VISIBLE FROM THE OCCUPIED AREAS THEY SERVE. |
| |
| 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| BUILDING. |
| |
| |